Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Model N252 EC Pendent for
Control Mode 
Speci

fi

 c Application (CMSA)

Bulletin 908 

Rev

. E

Bulletin 908 

Rev

. E

Model N252 (SIN RA0842)
Nominal K-Factor = 25.2

An Extended Coverage Sprinkler for 
Storage Applications

Features

 

1.  Approved by FM Global for the following storage 

applications:
Class 1-4, cartoned unexpanded plastic commodi-
ties under ceilings up to and including 35 feet (10.7 
m) high. They may be used to protect solid piled, 
palletized, shelf or bin box and open frame rack 
storage.*

2. For other storage commodities and storage ar-

rangements, see FM Global Data Sheets 8-9.

3.  Approved for installation per NFPA 13 (2013) . For 

storage commodities, arrangements, and design 
criteria: see NFPA 13 chapter 21.

4.  Eliminates the need for in-rack sprinklers.*
5.  Extended coverage, low pressure, and low flow 

demand provides the opportunity to reduce:
• Labor
•  Piping and fittings
•  Fire pump size
• Tank 

size

6.  165 °F (74 °C) and 212 °F (100 °C) temperature 

ratings.

7.  Maximum deflector distance from ceiling is 13

1

/

2

” 

(343mm). 12” (305mm) to center line of thermal ele-
ment.

8. This is a Quick Response CMSA sprinkler that 

meets the requirements of IFC 2015 for the elimi-
nation of smoke/heat vents in storage occupan-
cies.

9.  US Pat. No. 7,624,812

Other Patents Pending.

*

 See Design Criteria for details, Tables 1 & 2.

N252 EC Pendent

Listings and Approvals

FM Approved as a storage sprinkler.

Product Description

The Model N252 EC Pendent are Control Mode Specific 

Application Extended Coverage Sprinklers for Storage 
Applications. This includes protection of the storage  and 
display of Class I through IV commodities encapsulated 
or unencapsulated, cartoned unexpanded plastics. The 
Model N252 EC sprinklers offer maximum coverage areas 
up to 14 ft by 14 ft (196 ft

2

) as compared to ESFR or Stan-

dard Coverage Control Mode or Control Mode Specific 
Application sprinklers with maximum coverage of 100 ft

2

 

(9m

2

). This offers the advantage of decreasing the number 

of required sprinklers, reducing labor and material costs. 
The Model N252 EC Pendent Control Mode Specific Appli-
cation Sprinklers is designed  for use in ceiling only sprin-
kler systems with no in-rack sprinklers required. 

Table 1: Design Criteria for FM Class 4 and Cartoned Unexpanded Plastics in Open Frame Racks

Maximum

Building Height

Feet (m)

Maximum

Storage Height*

Feet (m)

Minimum

Pressure

Psi (bar)

Maximum

Spacing
Feet (m)

Number of 

Design

Sprinklers

Hose Stream

Allowance

GPM (L/min)

Water

Supply

Duration

25 (7,5)

20 (6,0)

25 (1.7)

14 x 14 (4,3 x 4,3)

6

250 (950)

1 Hour

30 (9,1)

25 (7,6)

30 (2.1)

14 x 14 (4,3 x 4,3)

6

250 (950)

1 Hour

35 (10,7)

30 (9,1)

40 (2.8)

12 x 12 (3,6 x 3,6)

8

250 (950)

1 Hour

*

 Storage must be a minimum of 3’ (0.9m) below the deflector