background image

The Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Bulletin 034 

Rev
.

 B

Bulletin 034 

Rev. 

B

Model G5-56, Model G5-42, 
Model G5-28
Quick Response Concealed
Automatic Sprinkler

UL Quick Response
FM Standard Response
Concealed Sprinkler With a 

3

/

4

” (19mm)  Adjustment

Features

1.  Cover plate attachment (Plain or Perforated) with 

¾” (19mm) assembly adjustment.

2.  Smooth aesthetic ceiling profile.
3.  Factory installed protective cap.
4.  Available in Chrome and White as Standard Finish-

es. Special Application Finishes are also available. 

5.  Ordinary and Intermediate temperature rating.

For additional Sprinklers refer to Bulletin 154 for 
Technical Speci

fi

 cation and Approvals

Approvals & Listings

1.  Underwriters Laboratories Inc. and cULus -

 Quick 

Response

• 

G5-56 - Light Hazard and Ordinary Hazard 
Occupancies

• 

G5-42 - Light Hazard Occupancies

• 

G5-28 - Light Hazard Occupancies

2.  Factory Mutual Research Corp. (FM) -

  Standard Response (See Page 3)

•  See the most recent FM Global Property 

Loss Prevention Data Sheets for installation  
and use guidelines.

3.  Loss Prevention Council (LPCB, UK) -

 Standard 

Response

• 

G5-56 - Light Hazard and Ordinary Hazard 
Occupancies

4.  VdS Schadenverhütung GmbH -

 Standard 

Response

5.  EC-Certificate of Conformity 0832-CPD-2062

U.S. Patent number 6,554,077.

Application 

The Reliable Model G5-56, G5-42 and G5-28 are the most 

versatile quick response concealed sprinklers available. It 
provides the best form of fire protection while offering an at-
tractive appearance and 

3

/

4

” (19mm) of cover adjustment for 

ease of installation. The small diameter cover plate assem-
bly is easily attached and blends into the ceiling, concealing 
the most dependable fire protection available, an automatic 
sprinkler system.

The Model G5-56, G5-42 and G5-28 are designed for use 

where aesthetic appearance is important. Offices, hospitals, 
motels and restaurants are but a few of the applications where 
it can be used. 

 The Model G5-56, G5-42 and G5-28 are UL Listed Quick 

Response Concealed sprinklers intended for use in accor-
dance with NFPA 13. FM Approves the G5-56 and the G5-28 
sprinkler as a standard response concealed sprinkler intended 
for use in accordance with FM Loss Prevention Data Sheet 2.0.

Product Description 

The Reliable Model G5-56, G5-42 and G5-28 uses a proven 

quick response fusible element in a standard style sprinkler 
frame with a drop-down deflector. This assembly is recessed 
into the ceiling and concealed by a flat cover plate assem-
bly. The threaded engagement provides ¾” (19mm) of cover 
adjustment. The flat cover plate is attached to the skirt using 
either 135°F (57°C) or 165°F (74°C) ordinary temperature clas-
sification solder.

When the ceiling temperature rises, the solder holding the 

flat cover plate melts, the flat cover plate released thus expos-
ing the sprinkler inside to the rising ambient temperature.

The subsequent fusing of the element opens the waterway 

and causes the deflector to distribute the water.  Any secure 
engagement between the cover plate and cup will assure that 
the drop-down deflector is properly located below the ceiling.

Plain Cover Plate

Perforated Cover Plate

Содержание G5-28

Страница 1: ...ring an at tractive appearance and 3 4 19mm of cover adjustment for ease of installation The small diameter cover plate assem bly is easily attached and blends into the ceiling concealing the most dependable fire protection available an automatic sprinkler system The Model G5 56 G5 42 and G5 28 are designed for use where aesthetic appearance is important Offices hospitals motels and restaurants ar...

Страница 2: ...uids Remove any sprinkler that has been painted other than factory applied or damaged in any way Concealed sprinklers cover plates can not be painted in the field after installation or have any other coating applied other than the factory finish A stock of spare sprinklers should be maintained to allow quick replacement of damaged or oper ated sprinklers Prior to installation sprinklers should be ...

Страница 3: ...2 8 40 NPT R 1 2 RA3411 For VdS Approval temperature rating sprinkler 165 F 74 c and cover plate 135 F 57 C only Notice FOR USE AS A REPLACEMENT OF MODEL G4A SPRINKLERS NOTE 1 Testing has shown that use of a nipple extension will not affect the listing of the sprinkler 2 For RETROFIT installations per NFPA 13 2010 section 8 15 19 4 which allows the use of nipples as the same pipe thread size as th...

Страница 4: ...throughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electri...

Отзывы: