background image

The Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Bulletin 162 

Rev
.

 D

Bulletin 162 

Rev.

 D

Model G4A-300
Quick Response
Concealed Automatic
300 psi (20,7 bar) Rated 
Sprinkler

The G4A-300 Concealer

®

A Quick Response Concealed Sprinkler 
with ½” (13mm) or 
1½” (38mm) Adjustment

Features

1.  Cover plate attachment (Plain or Perforated) with 

½” (13mm) total adjustment. Does not re-
quire clips or springs.

2.  Smooth aesthetic ceiling profile.
3.  Factory installed protective cap.
4.  Available in brass, chrome or black plated 

and white painted finishes.

5.  Ordinary temperature rating.
6.  300 psi (20,7 bar) maximum pressure rating.

Listings & Approvals

1.  Listed by Underwriters Laboratories, Inc. and Certified 

by UL for Canada (cULus) - Quick Response

2.  NYC - MEA - 258 - 93 - E 

Note:

 Approvals are for light and ordinary hazard.  The 

cup and skirt are fabricated from plated steel and are 
recommended for interior, non-corrosive applications.

Note:

 Paint or any other coatings applied over the factory 

finish will void all approvals and warranties.

US. Patent Number 4,880,063

The Model G4A-300 Concealer

®

 is designed for use where 

aesthetic appearance is important.  It can be used at working 
pressures up to 300 psi (20,7 bar).

The Model G4A-300 Concealer

®

 is a cULus Listed Quick 

Response Concealed Sprinkler intended for use in accor-
dance with NFPA 13.

Product Description

The Reliable Model G4A-300 Concealer

®

 uses a proven 

quick response fusible element in a standard style sprinkler 
frame with a drop-down deflector.  This assembly is recessed 
into the ceiling and concealed by a flat cover plate assembly.  
This threaded engagement provides ½” (13mm) of cover 
adjustment.  The flat cover plate is attached to the skirt us-
ing 135°F (57°C) ordinary temperature classification solder. 
When the ceiling temperature rises, the solder holding the flat 
cover plate melts, the flat cover plate released thus exposing 
the sprinkler inside to the rising ambient temperature.

The subsequent fusing of the solder element in the sprin-

kler opens the waterway and causes the deflector to drop 
into position to distribute the discharging water.  Any secure 
engagement between the cover plate and cup will assure 
that the drop-down deflector is properly located below the 
ceiling.

Application

The Reliable Model G4A-300  

Concealer

®

 is a versatile quick 

response concealed sprinkler. 

 

It provides the best form of fire 
protection while offering an at-
tractive appearance and ½” 
(13mm) cover plate adjustment 
for ease of installation. The small 
diameter cover plate assembly 
is easily attached and blends 
into the ceiling, concealing the 
most dependable fire protection, 
an automatic sprinkler system.

Отзывы: