background image

Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Model F1S5-FSLO with ½” threads
Model F1S5-FS56, Model F1S5-FS42
Special Response
Flat Spray Sprinklers

Bulle

tin 023 R

ev

. B
 

Bulletin 023 Rev. B 

Model F1S5-FSLO, K115, Large Orifice Flat Spray

-

Sprinkler
Types

Standard Pendent

Models F1S5-FS56, F1S5-FS42 and
F1S5-FSLO Flat Spray Sprinkler 
Types

Standard Pendent

Listings & Approvals

F1S5-FSLO

• 

VdS  Schadenverhütung  GmbH:  Certificate 

Gxxxxx

• 

CE  Certificate:  Standard  EN  12259-1,  Certificate  of 

constancy of performance 0786-CPR-xxxxx

F1S5-FS56

• 

VdS  Schadenverhütung  GmbH:  Certificate 

G4080046

• 

CE Certificate: Standard EN 12259-1, EC-Certificate 

of conformity 0786-CPD-40241

F1S5-FS42

• 

VdS  Schadenverhütung  GmbH:  Certificate 

G414024

• 

CE Certificate: Standard EN 12259-1, Certificate 

of constancy of performance 0786-CPR-40297

Product Description

The F1S5-FS56, F1S5-FS42 and F1S5-FSLO Flat Spray 

Sprinklers are designed for installation in accordance with 
CEA 4001 or EN 12845 (Automatic Sprinkler Systems - De-
sign, Installation and Maintenance). The spray pattern cre-
ated by this sprinkler makes this an excellent choice for ap-
plications with lower clearance above the suspended open 
ceilings and in racks.

The F1S5-FS56, F1S5-FS42 and F1S5-FSLO Flat Spray 

Sprinklers with shield  are used in applications where there 
are high and lower level sprinklers. The shield is to help pre-
vent the lower level sprinklers from getting wet by the higher 
level sprinklers.

The F1S5-FS56, F1S5-FS42 and F1S5-FSLO Flat Spray 

Sprinkler utilize a special response frangible 5.0mm glass 
bulb. The glass bulb consists of an accurately controlled 
amount of special fluid hermetically sealed inside of a pre-
cisely manufactured glass capsule. This glass bulb is special-
ly constructed to provide fast thermal response.

Pendent

Pendent with shield

At normal temperatures, the glass bulb contains the fluid 

in both the liquid phase and in the vapor phase. The vapor 
phase can be seen as a small bubble. As heat is applied, the 
liquid expands forcing the bubble smaller and smaller as the 
liquid pressure increases. Continued heating forces the liquid 
to push out against the bulb, causing the glass to shatter, 
opening the waterway and allowing the deflector to distribute 
the discharging water.

The F1S5-FS56, F1S5-FS42 and F1S5-FSLO Flat Spray 

Sprinkler  temperature  ratings  are  identified  by  the  color  of 

the glass bulb capsule.