background image

103 Fairview Park Drive, Elmsford, New York 10523

Bulletin 164

Rev.

B

Model F1FR-300/CCP
300 psi (20,7 bar) Rated
Concealed Quick
Response Sprinkler

Product Description

The Reliable Model F1FR-300/CCP Quick Response

Concealed Sprinkler is an attractive, low profile concealed
sprinkler assembly. This sprinkler assembly utilizes a
Model F1FR-300 pendent sprinkler in a Model CCP cup
and cover plate assembly. The cup is securely factory
threaded on the sprinkler inlet end.

The assembly is

shipped with a protective cap. The sprinkler and cup are
easily installed into the drop nipple using the Model RC1
Sprinkler Wrench. The cover plate assembly is attached to
the sprinkler cup using a cover plate assembly with flexible
tabs for threaded engagement. Simply push on the cover
plate, then turn to adjust or remove the cover plate
assembly.

The cover plate is attached to the skirt using 135

°

F

(57

°

C) or 165

°

F (74

°

C) ordinary temperature classification

solder. When the ceiling temperature rises, the solder
holding the cover plate melts, allowing the release of this
part and thus exposing the Model F1FR-300 sprinkler
inside to the rising ambient temperature.

The Model F1FR-300 automatic sprinkler utilizes a

3.0mm

frangible

glass

bulb.

This

sprinkler

has

demonstrated response times in laboratory tests which are
five times faster than standard responses sprinklers. This
quick response enables the Model F1FR-300 sprinkler to
apply water to a fire sooner than standard sprinklers of the
same temperature rating.

The glass bulb consists of an accurately controlled

amount of special fluid hermetically sealed inside a
precisely manufactured glass capsule constructed to
provide fast thermal response. The other sprinkler parts
are made of brass, copper and beryllium nickel.

At normal temperatures, the glass bulb contains the

fluid in both the liquid phase and vapor phase. The vapor
phase can be seen as a small bubble. As heat is applied
the liquid expands, forcing the bubble smaller and smaller
as the liquid pressure increases.

Continued heating

forces the liquid to push out against the bulb causing the
glass to shatter, opening the waterway and allowing the
deflector to distribute water.

The temperature rating of the sprinkler is identified by

the color of the glass bulb.

Application and Installation

The

Model

F1FR-300/CCP

Concealed

Sprinkler

Assembly uses a ½

²

(15mm) orifice, ½

²

NPT (R½), 135

°

F

(57

°

C), 155

°

F (68

°

C), 175

°

F (79

°

C), or 200

°

F (93

°

C) rated

Model F1FR-300 Pendent Sprinkler with a threaded Model
CCP cup, which is factory attached to the sprinkler. The
assembly is completed by the installation of an attractive,
low profile, 135

°

F (57

°

C) or 165

°

F (74

°

C) rated Model CCP

push on cover plate assembly.

The cover plate and

sprinkler cup assemblies are joined using a cover plate
with flexible tabs for threaded engagement. A choice of

B

u

lle

tin

1

6

4

R

e

v.

B

Features:

1. 300 psi (20,7 bar) rated.
2. Quick response performance.
3. Push on, thread off, sturdy, convenient

cover plate.

4. Factory assembled sprinkler and cup,

shipped complete with protective cap.

5. Sprinkler assembly and cover plate

separately packaged.

6. Two versions:

½" (13mm) Adjustment.

5

16

"

(8mm) Adjustment.

7. Rugged damage resistant assembly.

No exposed thermal element.

8. Utilizes Model F1FR-300 Pendent

Sprinkler.

9. Aesthetic ceiling profile.

10. Available in white or other color

painted; or brass, chrome or black
plated finishes.

Listings and Approvals

1. Underwriters Laboratories, Inc.
2. UL Certified for Canada.
3. NYC MEA 258-93-E

UL Listing Category

Sprinklers, Automatic and Open

-

Quick Response Concealed.