The Reliable Automatic Sprinkler Co., Inc.,

 103 Fairview Park Drive, Elmsford, New York 10523

Model DH56
Model DH56 Recessed
Model DH56 Concealed
Quick Response,
Extended Coverage Sprinkler

Bulle

tin 015 December 2021

Bulletin 015 December 2021

For coverages up to 28 feet wide and 10 
feet long

(1)

.  250 psi (17,2 bar) rated.

Features:

1.  Coverage for long and narrow spaces such as hall-

ways, corridors, decks and rooms up to 28 feet 
wide and 10 feet long.

(1)

2.  Deflector to ceiling dimensions are:

 4” (102mm) min. to 12” (305mm) max.

3.  Minimum spacing between sprinklers 14 feet 

(4.3m).

4.  Polyester Coated or  Electroless Nickel PTFE  Plat-

ed  Corrosion Resistant  Sprinklers 

 *Concealed Sprinkler is not corrosion resistant

5.  UL Listed for extended coverage, light hazard ap-

plications.  

6.  5.6  K  Factor.
7.  Sprinkler is approved for 250 psi (17,2 bar) appli-

cations.

8.  Quick response  performance.
9.  ½” (13mm) adjustment of escutcheon and cover.
10. Concealed cover plate can prevent the sprinkler 

from being used for unintended purposes. No ex-
posed thermal element with the concealed ver-
sion.

11. Push-on/thread-off sturdy convenient escutcheon 

for recessed and cover for concealed.

12. Factory assembled sprinkler & cup, shipped com-

plete with protective cap for concealed and FP re-
cessed versions.

13. Sprinkler & cup assembly and escutcheon or cov-

er are separately packaged.

14. 

Available in a variety of plated and painted finishes.

(1)

 See Figure 4.

Approval Organizations

1.  Listed by Underwriters Laboratories Inc. and 

UL certified for Canada (cULus)

2.  NYC MEA 258-93-E

Patents

US Patent No. 7,841,418
Other Patents Pending

DH56 FP Recessed

DH56

DH56 F2 Recessed

Products Description

The Model DH56 family of sprinklers are quick response 

extended coverage  sidewall sprinklers for use in light hazard 
applications.  The Model DH56 with SWC cover plate is a 
concealed sprinkler that uses Reliable’s push on/thread off 
sidewall cover. This sprinkler has the cup factory mounted 
and is shipped with a protective cap that protects the 3mm 

frangible glass bulb during shipping and post installation fin

-

ishing  operations.  The  DH56  can  be  combined  in  the  field 

with the FP or F2 Escutcheon to make a recessed sprinkler.  
The SWC cover plate, FP and F2 recessed escutcheons 
have ½” adjustment.  The SWC cover plate is attached with 

135-degree solder.  In the event of a fire the rising ambient 

temperature melts the solder and the cover plate is ejected 
away by springs exposing the 3mm frangible glass bulb.  The 
use of a 3mm bulb allows quick response which enables the 

sprinkler  to  apply  water  to  a  fire  sooner  than  standard  re

-

sponse sprinklers of the same temperature rating.

Application

The Model DH56 is a horizontal sidewall sprinkler intended for 

installation in light hazard occupancies in accordance with NFPA 

13.  These sprinklers are designed to provide fire protection in 

long and narrow spaces such as hallways, corridors, decks and 
rooms up to 28 feet (8,5m) wide and 10 feet (3m) long.  They are 
rated for 250 psi (17,2 bar) and can be mounted between 4 and 
12 inches (102 and 305mm) down from the ceiling. 

DH56 Concealed

with SWC coverplate