4.4 PROFIsafe Destination address “F_Dest_Add”
The PROFIsafe destination address corresponds to the F-parameter
F_Dest_Add
and defines an unique source address within a PROFIsafe cluster.
Valid addresses: 1…99, also see chapter “F_Source_Add / F_Dest_Add” on page 42.
4.4.1 Series 75 /
115
Destruction, damage and malfunction of the measuring system in case of
infiltration of foreign substances and damp!
The access to the address switches has to be locked after the settings
with the screw plug. Tighten firmly!
The PROFIsafe destination address
is adjusted by means of two BCD-
switches:
4.4.2 Series 88
Requirements
● An IP-address must have been assigned to the measuring system.
● Between client computer and measuring system (server) there must be an active
TCP/IP communication. After POWER ON a TCP socket server is started at IP-
port 60042.
● On the client computer the TCP socket client – software “TR Address Client” must
www.tr-electronic.de/f/zip/TR-ECE-SW-DGB-0002
● IP-address and MAC-address must be known. The MAC-address can be read
from the nameplate of the measuring system.
● From view of the client computer the connection is executed via a certain port
number. In this connection, the range of the port numbers can be between 49152
and 65535. It must be made sure that a firewall does not block the connection.
Procedure
Start TCP socket client.
Enter the IP-address and MAC-address valid for the device.
Enter desired PROFIsafe destination address
F_Dest_Add
.
Click
Send
button.
−
After successful execution the programmed PROFIsafe destination
address is confirmed.