3 Technical Data
3.1 Safety
Startup time ...................................................
Time between POWER-UP and safe position output
Overall system .........................................
≤
7 s with SIMATIC S7, CPU317F-2
PFH, "High demand" operating mode .........
1.46 * 10
–9
1/h
Scanning, double magnetic ......................
2.30*10
-9
1/h
PFD
av
(T
1
= 20 a) .............................................
1.27 * 10
–4
MTTF
d
high .....................................................
421 a
Scanning, double magnetic ......................
110 a
* DC
avg
high ....................................................
95 %
Scanning, double magnetic ......................
98.87 %
Internal process safety time .........................
Time between occurrence of an F-Error and alarm
indication
Overall system .........................................
≤
6.5 ms
Process safety angle.....................................
Angle between error occurrence and alarm indication
Via channel-internal self-diagnosis ..........
± 100 °, in relation to the measuring system shaft,
at 6000 min
-1
Through channel comparison ..................
Parameterizable with iParameter
Window increments
T
1
, Proof Test .................................................
20 years
* The assessment occurred in accordance with Note 2 on Table 6 of EN ISO 13849-1
3.2 Electrical characteristics
3.2.1 General
Supply voltage .......................................
13…27 V DC acc. to IEC 60364-4-41, SELV/PELV
Feed ..............................................
single feed input, but electrically separated internally
by means of two power supplies
Reverse polarity protection ...........
yes
Short-circuit protection ..................
yes, by internal 2 A safety fuse
Overvoltage protection ..................
yes, up to
≤
36 V DC
Current consumption without load ......
< 180 mA at 24 V DC
Option HTL-Level, 13…27 VDC ....
increased current consumption, see page 27