AI settings
DIP-switches 1-3 and 6 are used to adapt the actuator to different
signals and change the analogue input range. To switch from
voltage analogue input to current analogue input, the DIP switch 6
has to be set accordingly.
Action settings
DIP-switch 4 is used to set type of action.
Direct action
The signal increases when the actuator stem extends
DA (direct action)
Reverse action
The actuator stem retracts when the signal increases
RA (reverse action)
Stroke settings
DIP switches 5 is used to set the control characteristics. A linear curve is
recommended for valves with linear or equal percentage characteristics.
The almost equal percentage setting is recommended for quick opening
of 3 points valves.
Linear
Almost equal percentage (Eq%)
Use the jumper to choose and match the actuator’s stroke to the valve.
The factory setting for RVAPC-24A is 3.2 mm.
3.2 mm
6.3 mm
2