AI settings

DIP-switches 1-3 and 6 are used to adapt the actuator to different 

signals and change the analogue input range. To switch from  
voltage analogue input to current analogue input, the DIP switch 6 
has to be set accordingly.

Action settings

DIP-switch 4 is used to set type of action.

Direct action

The signal increases when the actuator stem extends

   

DA (direct action)

Reverse action

The actuator stem retracts when the signal increases

   

RA (reverse action)

Stroke settings

DIP switches 5 is used to set the control characteristics. A linear curve is 
recommended for valves with linear or equal percentage characteristics. 
The almost equal percentage setting is recommended for quick opening 
of 3 points valves.

 

Linear

Almost equal percentage (Eq%)

Use the jumper to choose and match the actuator’s stroke to the valve. 
The factory setting for RVAPC-24A is 3.2 mm.
 

3.2 mm

6.3 mm