INSTRUCTION
i
Read this instruction before installation
and wiring of the product
RVAN5-230
Valve actuator for 3-position control
RVAN5-230 is a valve actuator designed for control of Regin valves.
For more info, see the product sheet of each valve. The actuator can
also be combined with other brands of valves using adapter kits. The
actuator can be operated manually.
Technical data
Supply voltage
230 V AC ±15 %, 50 Hz
Control signal
3-position
Max. power consumption 15.3 W / 16.5 VA
Stroke
10...30 mm
Stroke time
3 s/mm
Force
500 N
Ambient temperature
0...50ºC
Storage temperature
-40...80°C
Ambient humidity
10...90 % RH
Dimensions
198 x 266 x 133 mm
Protection class
IP54
Mounting
If the valve stem lock and valve throat adaptor are not already mounted
on the valve, mount them. Pull the valve stem out as far as possible.
Remove the locking bolts and U-bolt from the actuator yoke.
Depress the spring-loaded tab on the drive rod coupling device and fit the
valve stem into the coupling. Release the tab to connect the valve to the
actuator.
The position of the yoke on the valve stem adaptor must be adjusted so
that the U-bolt mounting holes line up with the groove in the valve throat
adaptor. If the drive rod needs to be moved in or out for this, depress the
central button of the control knob and turn it clockwise to extend the drive
rod and anti-clockwise to retract it (see Manual override).
Mount the U-bolt and the nuts. Tighten the nuts until the actuator is firmly
attached. Disassembly takes place in reverse order.
Mounting positions
Wiring
1
2
3
Y1
N
Y2
Y1 sluten = Ställdonsspindeln skjuts ut
Y2 sluten = Ställdonsspindeln dras in
L N
230V AC
Calibration
Field calibration is not required. When the valve reaches an end posi-
tion and the actuator provides nominal positioning force, power to the
actuator motor is cut automatically.
Manual override
To manually set the valve position, first depress the central part of the
knob until it clicks in place and remains depressed (1 in the figure).
The valve position may then be changed manually by turning the
knob (2 in the figure). Clockwise rotation will extend the drive rod and
anti-clockwise rotation will retract it.
To return to normal operation, position the knob so that it is in line with
the text (Auto) on the cover. Then press down on the outer parts of
the knob (3 in the figure). The depressed central part will pop out and
the actuator will return to operation.
This product carries the CE-mark. More information is available at
www.regincontrols.com.
Contact
AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, [email protected]
RVAN5-230
10574D
MA
Y 18
EN
1
Y1 circuit closed = Actuator spindle
is extending from the actuator
Y2 circuit closed = Actuator spindle
is retracting into the actuator
90º
90º