Regio Midi manual
Chapter 17
Modbus signals
69
Chapter 17 Modbus signals
Discrete inputs
Signal name
Type
Modbus
address
Description
RC_Actual_L.RegioDigIn(0)
L,2
1
Not used
RC_Actual_L.RegioDigIn1
L,2
2
Value of digital input 1
RC_Actual_L.RegioDigIn2
L,2
3
Value of digital input 2
RC_Actual_L.RegioUDigIn1
L,2
4
Value of universal digital input 1
RC_Actual_L.RegioDigOut(0)
L,2
5
Not used
RC_Actual_L.RegioDigOut1
L,2
6
Value of digital output 1
RC_Actual_L.RegioDigOut2
L,2
7
Value of digital output 2
RC_Actual_L.RegioDigOut3
L,2
8
Value of digital output 3
RC_Actual_L.RegioDigOut4
L,2
9
Value of digital output 4
RC_Actual_L.RegioDigOut5
L,2
10
Value of digital output 5
RC_Actual_L.RegioUDigOut1
L,2
11
Value of universal digital output 1
RC_Actual_L.RegioUDigOut2
L,2
12
Value of universal digital output 2
RC_Actual_L.RegioDIOpenWindow
L,2
13
Indicate open window
RC_Actual_L.RegioDICondenseAlarm
L,2
14
Indicate condense alarm from digital input
RC_Actual_L.RegioDIPresences
L,2
15
Indicate presence from digital input
RC_Actual_L.RegioDIChangeOver
L,2
16
Indicate change over from digital input
RC_Actual_L.RegioFanSpeed1
L,2
17
Indicate fan speed 1
RC_Actual_L.RegioFanSpeed2
L,2
18
Indicate fan speed 2
RC_Actual_L.RegioFanSpeed3
L,2
19
Indicate fan speed 3
RC_Actual_L.RegioForcedventilation
L,2
20
Indicate forced ventilation
RC_Actual_L.RegioCVHeatPulsProp
L,2
21
Indicate pulse prop heating
RC_Actual_L.RegioCVCoolPulsProp
L,2
22
Indicate pulse prop cooling
RC_Actual_L.RegioCVHeatInc
L,2
23
Indicate increase heating
RC_Actual_L.RegioCVHeatDec
L,2
24
Indicate decrease heating
RC_Actual_L.RegioCVCoolInc
L,2
25
Indicate increase cooling
RC_Actual_L.RegioCVCoolDec
L,2
26
Indicate decrease cooling
RC_Actual_L.RegioAIChangeOverState
L,2
27
Indicate change-over state from analogue
input
RC_Actual_L.RegioChangeOverState
L,2
28
Indicate change-over state from both digital
and analogue input
Not used in this model
L,2
29
RC_Actual_L.RegioDigOut3
L,2
30
Value of universal digital output 3
RC_Actual_L.RegioPresence
L,2
31
Indicate presence
RC_Actual_L.RegioRoomTempHighTempAlarm L,2
32
Indicate high room temperature alarm
RC_Actual_L.RegioRoomTempLowTempAlarm
L,2
33
Indicate low room temperature alarm
RC_Actual_L.RegioDICO2
L,2
34
Indicate high CO
2
level