Regio Midi manual
Chapter 5
Installation preparations
13
Example 1
If the address on the sticker is 191:183 the following addresses are valid for the different
communication protocols:
EXOline: PLA=191, ELA=183
Modbus: address=183
BACnet: device ID=191183 (low 4 figures=1183, high 3 figures=19), MS/TP MAC
address=83*
Example 2
If the address on the sticker is 10:001 the following addresses are valid for the different
communication protocols:
EXOline: PLA=10, ELA=1
Modbus: address=1
BACnet: device ID=10001 (low 4 figures=1, high 3 figures=1), MS/TP MAC address=1*
*
BACnet is only available in models with display
Configuration
If you want to configure the unit, it is normally better to do this before sending the electronic
cassette to the installation site. The bottom plates with location and wiring information can be
sent separately in advance to the installation site for electric installation.
The controllers are normally configured using Regio tool
©
.
Models with a display can be configured via the parameter menu in the display, but the easiest
way to set parameters is via Regio tool
©
. See
Configuration using
Regio tool
©
below and the
chapter
Display handling
.
Models without a display have DIP switches for configuration. See the section
DIP switches
below.
Configuration using Regio tool
©
1.
Download Regio tool
©
to your computer
from www.regincontrols.com.
2.
Connect the computer to the back of the Regio cassette with an E-cable-USB or
equivalent.. The E-cable-USB is connected to terminals 42(A) and 43(B). Use a 24 V AC
transformer for supply voltage of the Regio cassette on terminals 10 and 11.
3.
Go to the
Device manager
on your computer and check which communication port that
the cable has been assigned.
4.
Open Regio tool
©
on your computer.
The passwords in Regio tool
©
for the various access
levels are 1111 (log in as administrator) and 3333 (log in as operator). For more
information, see the manual for Regio tool
©
.
5.
Go to the
Tools
menu in Regio tool
©
and
choose
Communication Settings
and the
Communication Channels
window will open up. Check that the
Default port
is the same
as assigned on the computer, otherwise change the port name in Regio tool
©.
6.
Each controller has a unique PLA- and ELA-address on delivery. If the PLA:ELA address
is unknown, go to the
Tools
menu and choose
Search For Controllers
. This function will
search through all the possible addresses until the Regio unit is detected.
7.
Set the controller address under the
Configuration
menu. The controller address should
be entered instead of the Regio tool
©
default address (254:30).
The computer and the Regio unit should now be in contact with each other.
8.
Start setting parameters and functions for the Regio. See the manual for Regio tool
©
for
more information.