3.7 Configuration settings
The room unit configuration settings are described in the following sections.
3.7.1
General
This section describes the general configuration settings.
Table 3-5 General configuration settings.
Configuration setting
Description
Connected room unit
The room unit model that is used in the room HVAC system:
✓
None
✓
ED-RU
✓
ED-RU-O
✓
ED-RU-F
✓
ED-RU-FO
✓
ED-RU-DO
✓
ED-RU-DFO
✓
ED-RU-DOS
✓
ED-RU-H
✓
ED-RU-DOCS
✓
ED-RUD
(Modbus)
This setting is used for configuration purposes, that is, for displaying relevant configura-
tion settings in Application tool that are related to the specific room unit model.
Room unit address
Specifies the room unit ELA or Modbus address that the controller uses for communi-
cation with the room unit.
The ELA address has the format 1:[1-30] and is printed on a label that is located on the
back of the room unit PCB.
0:
The controller automatically identifies the ELA address of the connected room unit
(default setting).
1, 2, 3...28, 29, 30:
The controller only communicates with a connected room unit that
has this ELA address.
3.7.2
Max setpoint adjustment
This section describes the max setpoint adjustment configuration settings.
Table 3-6 Max setpoint adjustment configuration settings.
Configuration setting
Description
Max setpoint adjustment up (°C)
Specifies the maximum allowed setpoint adjustment up.
Max setpoint adjustment down (°C)
Specifies the maximum allowed setpoint adjustment down.
3.7.3
Display
This section describes the display configuration settings.