Signal name
Object name
Instance
number
Writeable Description
RCPSettings.
RegioECFanOutputSelect
RegioECFanOutputSelect 30085
YES
Manual/Auto of ECFan
1=Off
2=Manual
3=Auto
RCPSettings.RegioLightSelect
RegioLightSelect
30104
YES
Manual/Auto of Lighting
1=Off
2=On
3=Auto
RCPSettings.
RegioSunBlindsInSelect
RegioSunBlindsInSelect
30105
YES
Manual/Auto of BlindIn
1=Off
2=On
3=Auto
RCPSettings.
RegioSunBlindsOutSelect
RegioSunBlindsOutSelect 30106
YES
Manual/Auto of BlindOut
1=Off
2=On
3=Auto
RCPSettings.
RegioForcedVentSelect
RegioForcedVentSelect
30107
YES
Manual/Auto of ForceVentilation
1=Off
2=On
3=Auto
RCPSettings.
RegioDigOutSelectSumAlarm
RegioDigOutSelectSumA-
larm
30108
YES
Manual/Auto of SumAlarm
1=Off
2=On
3=Auto
RCPSettings.
RegioDigOutSelectSumAlarmA
RegioDigOutSelectSumA-
larmA
30109
YES
Manual/Auto of SumAlarmA
1=Off
2=On
3=Auto
RCPSettings.
RegioDigOutSelectSumAlarmB
RegioDigOutSelectSumA-
larmB
30110
YES
Manual/Auto of SumAlarmB
1=Off
2=On
3=Auto
RCPSettings.
RegioForcedVentSelectZone2
RegioForcedVentSelect-
Zone2
30114
YES
Manual/Auto of ForceVentilation Zone2
1=Off
2=On
3=Auto
RCPSettings.RegioDigOutSelect-
SumAlarmAZone2
RegioDigOutSelectSumA-
larmAZone2
30116
YES
Manual/Auto of SumAlarmA Zone2
1=Off
2=On
3=Auto
RCPSettings.RegioDigOutSelect-
SumAlarmBZone2
RegioDigOutSelectSumA-
larmBZone2
30117
YES
Manual/Auto of SumAlarmB Zone2
1=Off
2=On
3=Auto
RCPSettings.RegioFanSelect
RegioFanSelect
30118
YES
Fan speed Selected Remote/RegioTool
1=Off
2=Speed1
3=Speed2
4=Speed3
5=Auto
RCPSettings.RegioRUTempUnit
RegioRUTempUnit
30120
YES
Display Unit
1=None
2=°C
3=°F
RCPActual.RegioControlState
RegioControlState
40027
NO
Current unit state
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
5=ByPass
Regio
Eedo
manual, Rev. D
99