Signal name
Modbus
address
Description
RCPActual.RegioFanSpeed3Output
13
Start Fan Speed 3
RCPActual.RegioLightingOutput
14
Start signal Lighting
RCPActual.RegioSunBlindsInOutput
15
In signal Blind
RCPActual.RegioSunBlindsOutOutput
16
Out signal Blind
RCPActual.RegioForcedVentOutput
17
Start forced ventilation
RCPActual.RegioHeat1IncOutput
18
Increase heat 1 valve
RCPActual.RegioHeat1DecOutput
19
Decrease heat 1 valve
RCPActual.RegioHeat1PulsPropOutput
20
Puls prop heat 1 valve
RCPActual.RegioHeat2IncOutput
21
Increase heat 2 valve
RCPActual.RegioHeat2DecOutput
22
Decrease heat 2 valve
RCPActual.RegioHeat2PulsPropOutput
23
Puls prop heat 2 valve
RCPActual.RegioCool1IncOutput
24
Increase cool 1 valve
RCPActual.RegioCool1DecOutput
25
Decrease cool 1 valve
RCPActual.RegioCool1PulsPropOutput
26
Puls prop cool 1 valve
RCPActual.RegioCool2IncOutput
27
Not used
RCPActual.RegioCool2DecOutput
28
Not used
RCPActual.RegioCool2PulsPropOutput
29
Not used
RCPActual.RegioHeatCoolIncOutput
30
Increase Heat cool valve
RCPActual.RegioHeatCoolDecOutput
31
Decrease Heat cool valve
RCPActual.RegioHeatCoolPulsPropOutput
32
Puls prop Heat cool valve
RCPActual.RegioSumAlarm
33
Sum alarm
RCPActual.RegioSumAlarmA
34
Sum alarm A
RCPActual.RegioSumAlarmB
35
Sum alarm B
RCPActual.RegioRoomTempControlState
36
Current controller state:
0=Heating
1=Cooling
RCPActual.RegioSunBlindsState
37
Blind Position:
0=In
1=Out
RCPActual.RegioPresence
38
Presence indication
RCPActual.RegioCO2Presence
39
Is set if presence if CO2 is high
RCPActual.RegioAIChangeOverState
40
Is set if change over from analog input
RCPActual.RegioChangeOverState
41
Is set if change over
RCPActual.RegioRoomTempSensorAlarm
42
Is set if sensor alarm on room sensor (Internal or external)
RCPActual.RegioTimeGroupOcc
43
Time Group 'Occupied' (No. 1).
RCPActual.RegioTimeGroupUnOcc
44
Time Group 'UnOccupied' (No. 2).
RCPActual.RegioTimeGroupLighting
45
Time Group 'Lighting' (No. 3).
RCPActual.RegioCool2IncOutputZone2
65
Not used
RCPActual.RegioCool2DecOutputZone2
66
Not used
RCPActual.RegioCool2PulsPropOutputZone2
67
Not used
RCPActual.RegioSumAlarmZone2
71
Sum alarm
RCPActual.RegioSumAlarmAZone2
72
Sum alarm A
RCPActual.RegioSumAlarmBZone2
73
Sum alarm B
RCPActual.RegioExerciseOnHeat1
85
Valve Heat 1 in exercise
RCPActual.RegioExerciseOnHeat2
86
Valve Heat 2 in exercise
96
Regio
Eedo