Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioRemovableWallsELASlave3
392
33
1
ELA Slave 3
RCPSettings.RegioRemovableWallsELASlave4
393
34
1
ELA Slave 4
RCPSettings.RegioNRetries
394
3
1
Number of retries to read/write var from/to slaves
RCPSettings.RegioSlaveCommTimeOut
395
3
1
Minutes with missed comunication from master to a
slave consider that there is a comm failure and
revert back to control it's own outputs
RCPSettings.RegioRemoteRoomTemp
396
0
10
Communication Room Temperature Value
RCPSettings.RegioRemoteAIChangeOver
397
0
10
Communication Changeover Temperature Value
RCPSettings.RegioRemoteOutDoorTemp
398
0
10
Communication Outdoor Temperature Value
RCPSettings.RegioRemoteCondense
399
0
1
Communication Condensation Value
RCPSettings.RegioRemoteRoomCO2
400
0
1
Communication CO2 Value
RCPSettings.RegioRemoteRoomRH
401
0
1
Communication RH Value
RCPSettings.RegioRemoteSupplyAir
402
0
10
Communication Supply Air Temperature Value
Qsystem.Sec
409
-
1
System Time Seconds
Qsystem.Minute
410
-
1
System Time Minutes
Qsystem.Hour
411
-
1
System Time Hours
Qsystem.WDay
412
-
1
System WeekDay
Qsystem.Week
413
-
1
System Week
Qsystem.Date
414
-
1
System Date Day
Qsystem.Month
415
-
1
System Date Month
Qsystem.Year
416
-
1
System Date Year
Qsystem.PLA
417
254
1
Controller PLA Address
Qsystem.ELA
418
30
1
Controller ELA Adress
AlaData.AlaPt1_Status
419
1
1
Status for point no. 1 Condensation
0=Not used
1=Normal
2=Blocked
3=Acknowledge
4=Not used
5=Cancelled
6=Not used
7=Alarm
AlaData.AlaPt2_Status
420
1
1
Status for point no. 2 CondensationRoom2
AlaData.AlaPt3_Status
421
1
1
Status for point no. 3 SensorAlarm
AlaData.AlaPt4_Status
422
1
1
Status for point no. 4 SensorAlarmRoom2
AlaData.AlaPt5_Status
423
1
1
Status for point no. 5 Presence
AlaData.AlaPt6_Status
424
1
1
Status for point no. 6 OpenWindow
AlaData.AlaPt8_Status
426
1
1
Status for point no. 8 OpenWindowsRoom2
AlaData.AlaPt9_Status
427
1
1
Status for point no. 9 RoomUnitError
AlaData.AlaPt10_Status
428
1
1
Status for point no. 10 RoomUnitErrorRoom2
AlaData.AlaPt11_Status
429
1
1
Status for point no. 11 Slave1CommFail
AlaData.AlaPt12_Status
430
1
1
Status for point no. 12 Slave2CommFail
AlaData.AlaPt13_Status
431
1
1
Status for point no. 13 Slave3CommFail
AlaData.AlaPt14_Status
432
1
1
Status for point no. 14 Slave4CommFail
AlaData.AlaPt15_Status
433
1
1
Status for point no. 15 RoomTempHigh
AlaData.AlaPt16_Status
434
1
1
Status for point no. 16 RoomTempLow
AlaData.AlaPt17_Status
435
1
1
Status for point no. 17 RoomTempDeviation
94
Regio
Eedo