Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioRUType
315
9
1
Room Unit attached to the controller:
0=None
1=ED-RU
2=ED-RU-O
3=ED-RU-F
4=ED-RU-FO
5=ED-RU-DO
6=ED-RU-DFO
7=ED-RU-DOS
8=ED-RU-H
9=ED-RU-DOCS
10=ED-RUD
RCPSettings.RegioRUUserELASelection
316
0
1
User ELA Selection for Room Unit: 0=Auto Detect
RCPSettings.RegioRUTempUnit
317
1
1
Display Unit:
0=None
1=°C
2=°F
RCPSettings.RegioRUTemperatureComp
318
0
1
Temperature Compensation for RU 1
RCPSettings.RegioRUDisplayViewType
319
0
1
Select view mode for the display:
0=Display value
1=Display Value with setpoint adjustment
2=Heat setpoint
3=Cool setpoint
4=Average cool/heat setpoint
5=Only setpoint offset
6=CO2 Level
RCPSettings.RegioRUDisplaySetPointType
320
0
1
Select view mode for the display when pressing
increase decrease button:
0=Setpoint offset
1=Controlling setpoint
2=Heat setpoint
3=Cool setpoint
RCPSettings.RegioRUSetPointAdjTimeOut
321
5
1
Timeout for setpoint adjustment (sec)
RCPSettings.RegioRUMenuTimeOut
322
10
1
Timeout for menu (sec)
RCPSettings.
RegioRUOnOffButtonLongPressTime
323
5
1
Time (sec) that On/Off button must be pushed
before Shutdown state
RCPSettings.RegioRUNoOfSelectMenus
324
8
1
Number of menus visible in the RU-DOS
RCPSettings.RegioRUNoOfDecimals
325
1
1
Number of decimal to be showed
RCPSettings.RegioRUDisplayBacklightTime
326
30
1
Time for backlight (sec)
RCPSettings.RegioRUButtonsUsed
327
7
1
Buttons that can be used in the RU
RCPSettings.RegioRUDisplayBacklightLow
328
20
1
Lightning Lo (0-255)
RCPSettings.RegioRUDisplayBacklightHigh
329
100
1
Lightning Hi (0-255)
RCPSettings.RegioRUDisplayContrast
330
15
1
Contrast (0-15)
RCPSettings.RegioAlarmHyst
349
0.2
10
Alarm hysteresis
RCPSettings.RegioRoomTempHighLimit
350
40
1
High room temp
RCPSettings.RegioRoomTempLowLimit
351
15
1
Low room temp
RCPSettings.RegioRoomTempMaxDeviationLimit 352
20
1
Max allowed difference between setpoint and room
temp before alarm
RCPSettings.RegioCondenseLimit
357
80
1
High limit for condense alarm
RCPSettings.RegioCondenseHyst
358
2
1
Condense alarm hysteresis
RCPSettings.RegioCO2MaxLimit
361
1500
1
Max CO2 Level for Alarm