Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioFanSpeed2Start
54
60
1
If higher controller output start fanspeed 2
RCPSettings.RegioFanSpeed3Start
55
100
1
If higher controller output start fanspeed 3
RCPSettings.RegioFanSpeedHyst
56
5
1
Hysteresis % for start/stop fan
RCPSettings.RegioRUNoOfFanSpeeds
57
3
1
Configured number of fanspeeds (1-3)
RCPSettings.RegioFanSwitchTime
58
2
1
Time (sec) before switching fan speed when
changed from RU
RCPSettings.RegioECFanMaxLimit
59
100
1
Max limit for the EC fan (0-100)
RCPSettings.RegioECFanMinLimit
60
10
1
Min limit for the EC fan (0-100)
RCPSettings.RegioECFanStartSpeed
61
15
1
Only will output values above this Speed
RCPSettings.RegioFanStopTime
62
120
1
Time (Sec) for the Fan Stop delay when Fan After-
Blow used
RCPSettings.RegioFanAfterBlowControl
63
0
1
If enabled the Fan will work FanStopTime after
Heat applied
0=Off
1=Heat1
2=Heat2
3=Heat1 or Heat2
RCPSettings.RegioFanAfterBlowMinSpeed
64
0
1
Minimum Fan Speed when FanafterBlow Active
RCPSettings.RegioKickStartTime
65
0
1
Time (Sec) to Kick Start the Fan, during this time
the fan will work at 100%. If 0 this function is not
active
RCPSettings.RegioBoostMode
66
2
1
Boost Function will work when on Heating (0)
Cooling (1) Both (2)
RCPSettings.RegioConfigFanBoostTime
67
0
1
Time (sec) [0 to 600 seconds] that the Boost Func-
tion is active. If 0 the boost function is disabled
RCPSettings.RegioShortStart
68
10
1
Time (sec) that the Fan runs in Max Speed
RCPSettings.RegioBoostPBand
69
5
1
P-band of the P-Controller of the Fan (just in Boost
Startup Mode)
RCPSettings.RegioLightControlFunction
70
0
1
Select light control function
0=Central controlled
1=Local Time controlled
2=Presence controlled
3=Time or Presence controlled
4=Central controlled or Presence controlled
RCPSettings.RegioSunBlindsRunTime
71
240
1
Run time for controlling the jalusi in/out (sec)
RCPSettings.RegioSunBlindsControl
72
0
1
Remote Control for the Jalusi:
0=Go In
1-Stop
2-Go out
RCPSettings.RegioVAVControlType
109
2
1
Control the VAV output:
0=By temperature
2=By CO2 level
3=By both, the highest need
RCPSettings.RegioAi1
143
0
1
Configuration for Analog Input 1
0=Disable
1=External room temp
2=ChangeOver temp
3=Outdoor temp
4=Condensation
5=CO2 sensor
6=RH sensor
7=Not used
8=Not used
9=Not used
11=Supply air Temp
102=Not used
107=Not used
108=Not used
109=Not used
Regio
Eedo
manual, Rev. D
87