Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioCool2OutputMinLimit
27
0
1
Not used
RCPSettings.RegioCool2OutputMaxLimit
28
100
1
Not used
RCPSettings.RegioVAVOutputMinLimitOff
29
0
1
Min Limit for VAV Output at off State
RCPSettings.RegioVAVOutputMinLimitUno
30
10
1
Min Limit for VAV Output at Unoccupied State
RCPSettings.RegioVAVOutputMinLimitStandby
31
10
1
Min Limit for VAV Output at Stanby State
RCPSettings.RegioVAVOutputMinLimitOcc
32
20
1
Min Limit for VAV Output at Occupied or Bypass
State
RCPSettings.RegioVAVOutputMaxLimit
33
100
1
Max Limit for VAV Output
RCPSettings.RegioChangeOverSelect
34
2
1
Select Change Over:
0=heating
1=cooling
2=Auto
RCPSettings.RegioChangeOverAIDiffHeat
35
3
1
The difference between the temperature in the
room and the media temperature for change over
to cooling
RCPSettings.RegioChangeOverAIDiffCool
36
4
1
The difference between the temperature in the
room and the media temperature for change over
to heating
RCPSettings.RegioChangeOverValveTime
37
600
1
The minimum time the valve is opend during
change over calculation
RCPSettings.RegioMaxAirFlowHeatDemand
38
0
1
Max Airflow on Heat Demand , if above 0% the max
ariflow function is enabled
RCPSettings.RegioForcedVentControlMode
39
3
1
Forced Ventilation Control Mode:
0=Off
1=Force Vent on Heat
2=Force Vent on Cool
3=Force Vent on Both Heat and Cool
RCPSettings.RegioForcedVentAtMaxOutput
40
0
1
Forced Ventilation on Max Heat/Cool/Both
0=Off
1=Forced Ventilation on Max Heat
2=Forced Ventilation on Max Cool
3=Forced Ventilation on Max Heat or Cool
RCPSettings.
RegioSupplyAirTempLimCascadeFactor
41
3
1
Cascade Factor for the Cascade PID
RCPSettings.
RegioSupplyAirTempLimHeatMinLimit
42
24
1
Min Setpoint for the Cascade PID in Heat Mode
RCPSettings.
RegioSupplyAirTempLimHeatMaxLimit
43
35
1
Max Setpoint for the Cascade PID in Heat Mode
RCPSettings.
RegioSupplyAirTempLimCoolMinLimit
44
12
1
Min Setpoint for the Cascade PID in Cool Mode
RCPSettings.
RegioSupplyAirTempLimCoolMaxLimit
45
24
1
Max Setpoint for the Cascade PID in Cool Mode
RCPSettings.
RegioSupplyAirTempLimFrostProtSetPoint
46
8
1
Supply Air Temp Frost Protection Temperature
RCPSettings.RegioCO2PBand
47
100
1
CO2 PID P Band
RCPSettings.RegioCO2ITime
48
100
1
CO2 PID I Time
RCPSettings.RegioCO2SetPoint
49
600
1
Setpoint for CO2 PI Controller in PPM
RCPSettings.RegioCO2PresenceLimit
50
800
1
Activate presence if CO2 is higher
RCPSettings.RegioCO2PresenceHyst
51
160
1
Diff for deactivate presence on CO2
RCPSettings.RegioFanControlMode
52
0
1
FanControl Mode
0=No control
1=Controlled by Heating
2=Controlled by cooling
3=Controlled by both heat and cooling
RCPSettings.RegioFanSpeed1Start
53
20
1
If higher controller output start fanspeed 1
86
Regio
Eedo
manual, Rev. D