Room unit display parameter lists
Parameter Signal name
Default
value
Units
Description
17
RCPSettings.RegioDo1
7
Configuration for Digital Output 1
0 =Disabled
1 =Fan speed 1
2 =Fan speed 2
3 =Fan speed 3
4 =Lighting
5 =Blind in
6 =Blind out
7 =Forced ventilation
8 =Heat valve Inc.
9 =Heat valve Dec
10=Heat valve thermal(PWM)
11=Heat valve 2 Inc.
12=Heat valve 2 Dec.
13=Heat valve 2 thermal(PWM)
14=Cool valve Inc.
15=Cool valve Dec.
16=Cool valve thermal(PWM)
17=Not used
18=Not used
19=Not used
20=Change over valve Inc
21=Change over valve Dec
22=Change over thermal(PWM)
23=SumAlarm
24=SumAlarm A
25=SumAlarm B
117=Not used
118=Not used
119=Not used
18
RCPSettings.RegioDo2
23
-
Configuration for Digital Output 2
19
RCPSettings.RegioDo3
0
-
Configuration for Digital Output 3
20
RCPSettings.RegioDo4
0
Configuration for Digital Output 4
21
RCPSettings.RegioDo5
0
Configuration for Digital Output 5
22
RCPSettings.RegioDo6
0
Configuration for Digital Output 6
23
RCPSettings.RegioAi1Comp
0
°C
Analog input 1 compensation
24
RCPSettings.RegioAi2Comp
0
°C
Analog input 2 compensation
25
RCPSettings.RegioAi3Comp
0
°C
Analog input 3 compensation
26
RCPSettings.RegioAi4Comp
0
°C
Analog input 4 compensation
27
RCPSettings.RegioInternalTempComp
0
°C
Internal temperature sensor compensation
B.8 ALAM
Parameter Signal name
Default
value
Units
Description
1
RCPSettings.RegioAlarmHyst
0.2
Alarm hysteresis
2
RCPSettings.RegioRoomTempHighLimit
40
High room temp
3
RCPSettings.RegioRoomTempLowLimit
15
Low room temp
4
RCPSettings.RegioRoomTempMaxDeviationLimit
20
Max allowed difference between setpoint and
room temp before alarm
8
RCPSettings.
RegioRoomTempMaxDeviationLimitZone2
20
Max allowed difference between setpoint and
room temp before alarm Zone2
9
RCPSettings.RegioCondenseLimit
80
High limit for condense alarm
10
RCPSettings.RegioCondenseHyst
2
Condense alarm hysteresis
13
RCPSettings.RegioCO2MaxLimit
1500
ppm
Max CO2 Level for Alarm
Regio
Eedo
manual, Rev. D
79