Room unit display parameter lists
Parameter Signal name
Default
value
Units
Description
9
RCPSettings.RegioFanAfterBlowMinSpeed
0
Minimum Fan Speed when FanafterBlow
Active
17
RCPSettings.RegioFanStopTimeZone2
120
sec
Time (Sec) for the Fan Stop delay when Fan
AfterBlow used
18
RCPSettings.RegioFanAfterBlowMinSpeedZone2
0
Minimum Fan Speed when FanafterBlow
Active
B.5 M/AT
Parameter Signal name
Default
value
Units
Description
1
RCPSettings.RegioLightManual
0
Controls the light when central control
2
RCPSettings.RegioSunBlindsControl
0
Remote Control for the Jalusi:
0=Go In
1=Stop
2=Go out
5
RCPSettings.RegioHeat1OutputSelect
2
Manual/Auto of Heat1
0=Off
1=Manual
2=Auto
6
RCPSettings.RegioHeat2OutputSelect
2
Manual/Auto of Heat2
7
RCPSettings.RegioCoolOutputSelect
2
Manual/Auto of Cool1
8
RCPSettings.RegioHeatCoolOutputSelect
2
Manual/Auto of Heat Cool
9
RCPSettings.RegioVAVOutputSelect
2
Manual/Auto of VAV
10
RCPSettings.RegioECFanOutputSelect
2
Manual/Auto of ECFan
17
RCPSettings.RegioHeat1OutputManual
0
%
Manual value Heat 1
18
RCPSettings.RegioHeat2OutputManual
0
%
Manual value Heat 2
19
RCPSettings.RegioCoolOutputManual
0
%
Manual value Cool
20
RCPSettings.RegioHeatCoolOutputManual
0
%
Manual value Heat Cool
21
RCPSettings.RegioVAVOutputManual
0
%
Manual value VAV
22
RCPSettings.RegioECFanOutputManual
0
%
Manual value ECFan
29
RCPSettings.RegioLightSelect
2
Manual/Auto of Lighting:
0=Off
1=On
2=Auto
30
RCPSettings.RegioSunBlindsInSelect
2
Manual/Auto of BlindIn
31
RCPSettings.RegioSunBlindsOutSelect
2
Manual/Auto of BlindOut
32
RCPSettings.RegioForcedVentSelect
2
Manual/Auto of ForceVentilation
33
RCPSettings.RegioDigOutSelectSumAlarm
2
Manual/Auto of SumAlarm
34
RCPSettings.RegioDigOutSelectSumAlarmA
2
Manual/Auto of SumAlarmA
35
RCPSettings.RegioDigOutSelectSumAlarmB
2
Manual/Auto of SumAlarmB
43
RCPSettings.RegioFanSelect
4
Fan speed Selected Remote/RegioTool:
0=Off
1=Speed1
2=Speed2
3=Speed3
4=Auto
44
RCPSettings.RegioFanSelectZone2
4
Fan speed Selected Remote/RegioTool
0=Off
1=Speed1
2=Speed2
3=Speed3
4=Auto
76
Regio
Eedo
manual, Rev. D