Room unit display parameter lists
Parameter Signal name
Default
value
Units
Description
6
RCPSettings.RegioVAVOutputMinLimitOffZone2
0
%
Min Limit for VAV Output at off State Zone2
7
RCPSettings.RegioVAVOutputMinLimitUnoZone2
10
%
Min Limit for VAV Output at Unoccupied State
Zone2
8
RCPSettings.
RegioVAVOutputMinLimitStandbyZone2
10
%
Min Limit for VAV Output at Stanby State
Zone2
11
RCPSettings.RegioHeatValve1Type
0
Output Signal for HeatValve1:
0=0-10V
1=2-10V
2=10-2V
3=10-0V
4=Inc/Dec
5=PWM(Thermal)
6=6 Way-vay valve
12
RCPSettings.RegioHeatValve2Type
0
Output Signal for HeatValve2:
13
RCPSettings.RegioCoolValve1Type
0
Output Signal for CoolValve1:
14
RCPSettings.RegioCoolValve2Type
0
Output Signal for CoolValve2:
15
RCPSettings.RegioHeatCoolValveType
0
Output Signal for ChangeOver/6-WayValve
16
RCPSettings.RegioVAVType
0
Output Signal for VAV
17
RCPSettings.RegioECFANType
0
Output Signal for EC-Fan
25
RCPSettings.RegioCVHeatExerciseDay
8
Day for exercise heating and heat/cool valve:
0=Never
1-7=mon-sun
8=every day
26
RCPSettings.RegioCVCoolExerciseDay
8
Day for exercise cooling valve:
0=Never
1-7=mon-sun
8=every day
27
RCPSettings.RegioCVHeatExerciseHour
15
hour
Hour for exercise heating and heat/cool valve
28
RCPSettings.RegioCVCoolExerciseHour
15
hour
Hour for exercise cooling valve
29
RCPSettings.RegioHeatExerciseTime
120
sec
Time in seconds to Exercise the Heat Valves
30
RCPSettings.RegioCoolExerciseTime
120
sec
Time in seconds to Exercise the Cool Valves
B.4 FAN
Parameter Signal name
Default
value
Units
Description
1
RCPSettings.RegioFanControlMode
0
FanControl Mode
0=No control
1=Controlled by Heating
2=Controlled by cooling
3=Controlled by both heat and cooling
2
RCPSettings.RegioFanSpeed1Start
20
%
If higher controller output start fanspeed 1
3
RCPSettings.RegioFanSpeed2Start
60
%
If higher controller output start fanspeed 2
4
RCPSettings.RegioFanSpeed3Start
100
%
If higher controller output start fanspeed 3
5
RCPSettings.RegioFanSpeedHyst
5
%
Hysteresis % for start/stop fan
6
RCPSettings.RegioRUNoOfFanSpeeds
3
Configured number of fanspeeds (1-3)
7
RCPSettings.RegioMinFanSpeed
0
Min Speed for the fan:
0=Stop
1=Speed 1
8
RCPSettings.RegioFanStopTime
120
sec
Time (Sec) for the Fan Stop delay when Fan
AfterBlow used
Regio
Eedo
manual, Rev. D
75