Signal name
Object name
Instance
number
Writeable Description
RCPSettings.RegioSupplyAirTem-
pLimCoolMinLimit
RegioSupplyAirTempLim-
CoolMinLimit
30023
YES
Min Setpoint for the Cascade PID in Cool
Mode
RCPSettings.RegioSupplyAirTem-
pLimCoolMaxLimit
RegioSupplyAirTempLim-
CoolMaxLimit
30024
YES
Max Setpoint for the Cascade PID in Cool
Mode
RCPSettings.RegioSupplyAirTem-
pLimFrostProtSetPoint
RegioSupplyAirTempLim-
FrostProtSetPoint
30025
YES
Supply Air Temp Frost Protection
Temperature
RCPSettings.RegioCO2PBand
RegioCO2PBand
30026
YES
CO2 PID P Band
RCPSettings.RegioCO2ITime
RegioCO2ITime
30027
YES
CO2 PID I Time
RCPSettings.RegioCO2SetPoint
RegioCO2SetPoint
30028
YES
Setpoint for CO2 PI Controller in PPM
RCPSettings.RegioFanStopTime
RegioFanStopTime
30029
YES
Time (Sec) for the Fan Stop delay when Fan
AfterBlow used
RCPSettings.
RegioCVHeatExerciseDay
RegioCVHeatExerciseDay 30062
YES
Day for exercise heating and heat/cool
valve, 1=Never, 2-8=mon-sun, 9=every day
RCPSettings.
RegioCVCoolExerciseDay
RegioCVCoolExerciseDay 30063
YES
Day for exercise cooling valve
RCPSettings.
RegioCVHeatExerciseHour
RegioCVHeatExercise-
Hour
30064
YES
Hour for exercise heating and heat/cool
valve
RCPSettings.
RegioCVCoolExerciseHour
RegioCVCoolExercise-
Hour
30065
YES
Hour for exercise cooling valve
RCPSettings.
RegioHeatExerciseTime
RegioHeatExerciseTime
30066
YES
Time in seconds to Exercise the Heat
Valves
RCPSettings.
RegioCoolExerciseTime
RegioCoolExerciseTime
30067
YES
Time in seconds to Exercise the Cool Valves
RCPSettings.RegioAi1Comp
RegioAi1Comp
30074
YES
Analog input 1 compensation
RCPSettings.RegioAi2Comp
RegioAi2Comp
30075
YES
Analog input 2 compensation
RCPSettings.RegioAi3Comp
RegioAi3Comp
30076
YES
Analog input 3 compensation
RCPSettings.RegioAi4Comp
RegioAi4Comp
30077
YES
Analog input 4 compensation
RCPSettings.
RegioInternalTempComp
RegioInternalTempComp
30078
YES
Internal temperature sensor compensation
RCPSettings.
RegioHeat1OutputManual
RegioHeat1OutputManual 30092
YES
Manual value Heat 1
RCPSettings.
RegioHeat2OutputManual
RegioHeat2OutputManual 30093
YES
Manual value Heat 2
RCPSettings.
RegioCoolOutputManual
RegioCoolOutputManual
30094
YES
Manual value Cool
RCPSettings.
RegioHeatCoolOutputManual
RegioHeatCoolOutputMa-
nual
30095
YES
Manual value Heat Cool
RCPSettings.
RegioVAVOutputManual
RegioVAVOutputManual
30096
YES
Manual value VAV
RCPSettings.
RegioECFanOutputManual
RegioECFanOutputMa-
nual
30097
YES
Manual value ECFan
RCPSettings.RegioRUButtonsUsed RegioRUButtonsUsed
30121
YES
Buttons that can be used in the RU
RCPSettings.RegioAlarmHyst
RegioAlarmHyst
30124
YES
Alarm hysteresis
RCPSettings.
RegioRoomTempHighLimit
RegioRoomTempHighLimit 30125
YES
High room temp
RCPSettings.
RegioRoomTempLowLimit
RegioRoomTempLowLimit 30126
YES
Low room temp
RCPSettings.
RegioRoomTempMaxDeviationLimit
RegioRoomTempMaxDe-
viationLimit
30127
YES
Max allowed difference between setpoint
and room temp before alarm
RCPSettings.RegioCondenseLimit
RegioCondenseLimit
30132
YES
High limit for condense alarm
RCPSettings.RegioCondenseHyst
RegioCondenseHyst
30133
YES
Condense alarm hysteresis
104
Regio
Eedo
manual, Rev. D