Signal name
Object name
Instance
number
Writeable Description
RCPActual.RegioHeat1IncOutput
RegioHeat1IncOutput
20018
NO
Increase heat 1 valve
RCPActual.RegioHeat1DecOutput
RegioHeat1DecOutput
20019
NO
Decrease heat 1 valve
RCPActual.
RegioHeat1PulsPropOutput
RegioHeat1PulsPro-
pOutput
20020
NO
Puls prop heat 1 valve
RCPActual.RegioHeat2IncOutput
RegioHeat2IncOutput
20021
NO
Increase heat 2 valve
RCPActual.RegioHeat2DecOutput
RegioHeat2DecOutput
20022
NO
Decrease heat 2 valve
RCPActual.
RegioHeat2PulsPropOutput
RegioHeat2PulsPro-
pOutput
20023
NO
Puls prop heat 2 valve
RCPActual.RegioCool1IncOutput
RegioCool1IncOutput
20024
NO
Increase cool 1 valve
RCPActual.RegioCool1DecOutput
RegioCool1DecOutput
20025
NO
Decrease cool 1 valve
RCPActual.
RegioCool1PulsPropOutput
RegioCool1PulsPro-
pOutput
20026
NO
Puls prop cool 1 valve
RCPActual.RegioCool2IncOutput
RegioCool2IncOutput
20027
NO
Not used
RCPActual.RegioCool2DecOutput
RegioCool2DecOutput
20028
NO
Not used
RCPActual.
RegioCool2PulsPropOutput
RegioCool2PulsPro-
pOutput
20029
NO
Not used
RCPActual.
RegioHeatCoolIncOutput
RegioHeatCoolIncOutput
20030
NO
Increase Heat cool valve
RCPActual.
RegioHeatCoolDecOutput
RegioHeatCoolDecOutput 20031
NO
Decrease Heat cool valve
RCPActual.
RegioHeatCoolPulsPropOutput
RegioHeatCoolPulsPro-
pOutput
20032
NO
Puls prop Heat cool valve
RCPActual.RegioSumAlarm
RegioSumAlarm
20033
NO
Sum alarm
RCPActual.RegioSumAlarmA
RegioSumAlarmA
20034
NO
Sum alarm A
RCPActual.RegioSumAlarmB
RegioSumAlarmB
20035
NO
Sum alarm B
RCPActual.
RegioRoomTempControlState
RegioRoomTempControl-
State
20036
NO
Current controller state 1=Heating, 2=
Cooling
RCPActual.RegioSunBlindsState
RegioSunBlindsState
20037
NO
Blind Position 1=In 2=Out
RCPActual.RegioPresence
RegioPresence
20038
NO
Presence indication
RCPActual.RegioCO2Presence
RegioCO2Presence
20039
NO
Is set if presence if CO2 is high
RCPActual.
RegioAIChangeOverState
RegioAIChangeOverState 20040
NO
Is set if change over from analog input
RCPActual.RegioChangeOverState RegioChangeOverState
20041
NO
Is set if change over
RCPActual.
RegioRoomTempSensorAlarm
RegioRoomTempSensorA-
larm
20042
NO
Is set if sensor alarm on room sensor
(Internal or external)
RCPActual.RegioTimeGroupOcc
RegioTimeGroupOcc
20043
NO
Time Group 'Occupied' (No. 1).
RCPActual.RegioTimeGroupUnOcc RegioTimeGroupUnOcc
20044
NO
Time Group 'UnOccupied' (No. 2).
RCPActual.
RegioTimeGroupLighting
RegioTimeGroupLighting
20045
NO
Time Group 'Lighting' (No. 3).
RCPActual.RegioExerciseOnHeat1 RegioExerciseOnHeat1
20085
NO
Valve Heat 1 in exercise
RCPActual.RegioExerciseOnHeat2 RegioExerciseOnHeat2
20086
NO
Valve Heat 2 in exercise
RCPActual.RegioExerciseOnCool1
RegioExerciseOnCool1
20087
NO
Valve Cool 1 in exercise
RCPActual.RegioExerciseOnCool2
RegioExerciseOnCool2
20088
NO
Not used
RCPActual.
RegioExerciseOnHeatCool
RegioExerciseOnHeat-
Cool
20089
NO
Valve HeatCool in exercise
RCPActual.
RegioDIOpenWindowCombined
RegioDIOpenWindow-
Combined
20095
NO
Open window indication all Controllers
RCPActual.
RegioDICondenseAlarmCombined
RegioDICondenseAlarm-
Combined
20096
NO
Alarm Condens indication all Controllers