Signal name
Object name
Instance
number
Writeable Description
AlaData.AlaPt20_Status
AlaPt20_Status
30165
YES
Status for point no. 20
RoomTempLowZone2
AlaData.AlaPt21_Status
AlaPt21_Status
30166
YES
Status for point no. 21
RoomTempDeviationZone2
AlaData.AlaPt22_Status
AlaPt22_Status
30167
YES
Status for point no. 22
RoomControllerInManualModeZone2
AlaData.AlaPt23_Status
AlaPt23_Status
30168
YES
Status for point no. 23 MasterCommFail
AlaData.AlaPt24_Status
AlaPt24_Status
30169
YES
Status for point no. 24
SlaveNormalOperation
AlaData.AlaPt25_Status
AlaPt25_Status
30170
YES
Status for point no. 25 CO2 Level High
AlaData.AlaPt26_Status
AlaPt26_Status
30171
YES
Status for point no. 26 CO2 Level High
Zone2
D.2 Binary values
Signal name
Object name
Instance
number
Writeable Description
RCPSettings.RegioLightManual
RegioLightManual
10001
YES
Controls the light when central control
RCPSettings.
RegioLightingCmdRemote
RegioLightingCmdRemote 10002
YES
Remote Light Control
RCPSettings.
RegioRUConfigMenuDisable
RegioRUConfigMenuDis-
able
10005
YES
Enable entering the configuration menu in
the RU unit when pressing the UP and
Down Key
RCPSettings.
RegioRUConfigMenuDisableZone2
RegioRUConfigMenuDisa-
bleZone2
10006
YES
Enable entering the configuration menu in
the RU unit when pressing the UP and
Down Key
RCPSettings.RegioForceDisplayID
RegioForceDisplayID
10007
YES
Forces the Display to identify themselves
(show number on display/blink leds), can
leave this state by pressing On/Off button
RCPSettings.
RegioAutoSummerTime
RegioAutoSummerTime
10008
YES
Switch automaticly between summer and
winter time
RCPActual.RegioOpenWindowInd
RegioOpenWindowInd
20001
NO
Open window indication
RCPActual.
RegioCondensationAlarm
RegioCondensationAlarm
20002
NO
Alarm Condensation indication
RCPActual.RegioPresenceInd
RegioPresenceInd
20003
NO
Pressens indication
RCPActual.RegioChangeOverInd
RegioChangeOverInd
20004
NO
Change over indication
RCPActual.RegioDigOut1
RegioDigOut1
20005
NO
Digital output 1
RCPActual.RegioDigOut2
RegioDigOut2
20006
NO
Digital output 2
RCPActual.RegioDigOut3
RegioDigOut3
20007
NO
Digital output 3
RCPActual.RegioDigOut4
RegioDigOut4
20008
NO
Digital output 4
RCPActual.RegioFanSpeed1Output RegioFanSpeed1Output
20011
NO
Start Fan Speed 1
RCPActual.RegioFanSpeed2Output RegioFanSpeed2Output
20012
NO
Start Fan Speed 2
RCPActual.RegioFanSpeed3Output RegioFanSpeed3Output
20013
NO
Start Fan Speed 3
RCPActual.RegioLightingOutput
RegioLightingOutput
20014
NO
Start signal Lighting
RCPActual.
RegioSunBlindsInOutput
RegioSunBlindsInOutput
20015
NO
In signal Blind
RCPActual.
RegioSunBlindsOutOutput
RegioSunBlindsOutOutput 20016
NO
Out signal Blind
RCPActual.RegioForcedVentOutput RegioForcedVentOutput
20017
NO
Start forced ventilation
Regio
Eedo
manual, Rev. D
101