Signal name
Object name
Instance
number
Writeable Description
RCPActual.RegioHeatCoolSymbol
RegioHeatCoolSymbol
40028
NO
Current controller state
1=Off
2=Heating
3=Cooling
4=Heating and Cooling
RCPActual.RegioFanSpeed
RegioFanSpeed
40035
NO
Current 3speed fan speed
1=Off
2=Speed1
3=Speed2
4=Speed3
RCPActual.
RegioFanSpeedSelectCombined
RegioFanSpeedSelect-
Combined
40037
NO
Fan speed Selected
1=Off
2=Speed1
3=Speed2
4=Speed3
5=Auto
RCPActual.RegioMasterSlaveState RegioMasterSlaveState
40039
NO
Current State in Removable Walls Feature
1=StandAlone
2=Master
3=Slave
4=Slave with comm error running as
standalone
RCPActual.
RegioHeatCoolSymbolZone2
RegioHeatCoolSymbol-
Zone2
40056
NO
Current controller state
1=Off
2=Heating
3=Cooling
4=Heating and Cooling
AlaData.AlaPt1_Status
AlaPt1_Status
30146
YES
Status for point no. 1 Condensation
1=Not used
2=Normal
3=Blocked
4=Acknowledge
5=Not used
6=Cancelled
7=Not used
8=Alarm
AlaData.AlaPt2_Status
AlaPt2_Status
30147
YES
Status for point no. 2 CondensationZone2
AlaData.AlaPt3_Status
AlaPt3_Status
30148
YES
Status for point no. 3 SensorAlarm
AlaData.AlaPt4_Status
AlaPt4_Status
30149
YES
Status for point no. 4 SensorAlarmZone2
AlaData.AlaPt5_Status
AlaPt5_Status
30150
YES
Status for point no. 5 Presence
AlaData.AlaPt6_Status
AlaPt6_Status
30151
YES
Status for point no. 6 OpenWindow
AlaData.AlaPt7_Status
AlaPt7_Status
30152
YES
Status for point no. 7 PresenceZone2
AlaData.AlaPt8_Status
AlaPt8_Status
30153
YES
Status for point no. 8 OpenWindowsZone2
AlaData.AlaPt9_Status
AlaPt9_Status
30154
YES
Status for point no. 9 RoomUnitError
AlaData.AlaPt10_Status
AlaPt10_Status
30155
YES
Status for point no. 10 RoomUnitErrorZone2
AlaData.AlaPt11_Status
AlaPt11_Status
30156
YES
Status for point no. 11 Slave1CommFail
AlaData.AlaPt12_Status
AlaPt12_Status
30157
YES
Status for point no. 12 Slave2CommFail
AlaData.AlaPt13_Status
AlaPt13_Status
30158
YES
Status for point no. 13 Slave3CommFail
AlaData.AlaPt14_Status
AlaPt14_Status
30159
YES
Status for point no. 14 Slave4CommFail
AlaData.AlaPt15_Status
AlaPt15_Status
30160
YES
Status for point no. 15 RoomTempHigh
AlaData.AlaPt16_Status
AlaPt16_Status
30161
YES
Status for point no. 16 RoomTempLow
AlaData.AlaPt17_Status
AlaPt17_Status
30162
YES
Status for point no. 17 RoomTempDeviation
AlaData.AlaPt18_Status
AlaPt18_Status
30163
YES
Status for point no. 18
RoomControllerInManualMode
AlaData.AlaPt19_Status
AlaPt19_Status
30164
YES
Status for point no. 19
RoomTempHighZone2
100
Regio
Eedo