Room unit display parameter lists
Parameter Signal name
Default
value
Units
Description
25
RCPSettings.RegioForceDisplaySearch
-
Trigger a search for display on display port
26
RCPSettings.RegioSwapDisplayAddress
-
Swap the addres of the display. RU in Room1
will go to Room2 and ViceVersa. Only possible
with two display detected and Dual Zone
Active
B.7 IO
Parameter Signal name
Default
value
Units
Description
1
RCPSettings.RegioAi1
0
Configuration for Analog Input 1
0=Disable
1=External room temp
2=ChangeOver temp
3=Outdoor temp
4=Condensation
5=CO2 sensor
6=RH sensor
7=Not used
8=Not used
9=Not used
11=Supply air Temp
101=External room temp room 2
102=Not used
103=Outdoor temp room 2
104=Condensation room 2
105=CO2 sensor room 2
106=RH sensor room 2
107=Not used
108=Not used
109=Not used
111=Supply air temp room 2
2
RCPSettings.RegioAi2
0
Configuration for Analog Input 2
3
RCPSettings.RegioAi3
0
Configuration for Analog Input 3
4
RCPSettings.RegioAi4
0
Configuration for Analog Input 4
5
RCPSettings.RegioDi1
3
Configuration for Digital Input 1
0=Disable
1=Open window
2=Not Used
3=Presence detector
4=Changeover
101=Open window room 2
102=Not used
103=Presence detector room 2
6
RCPSettings.RegioDi2
1
Configuration for Digital Input 2
7
RCPSettings.RegioDi3
0
Configuration for Digital Input 3
8
RCPSettings.RegioDi4
0
Configuration for Digital Input 4
11
RCPSettings.RegioCI
1
Configuration for Digital Condensation Input 1:
0=Disable
1=Regin's KG-A/1 sensor
2=Regin's KG-A/1 sensor room 2
12
RCPSettings.RegioCI2
0
Configuration for Digital Condensation Input 2
Regio
Ardo
manual, Rev. D
87