Table 3-6 Two rooms support functions.
Configuration setting
Description
Show room unit ID
Disabled:
The room units do not indicate their room unit IDs (default setting).
Enabled:
The room units indicate their room unit IDs.
For room units without display, the LED in the centre of the room unit blinks. One slow
blink indicates ID 1 and two fast blinks indicate ID 2.
For room units with display, ID 1 and ID 2 are shown in the displays.
When the indications are shown in room units with display, the IDs can be swapped
between the room units by pressing the up or down button on any of the room units.
The indications are shown until the occupancy (on/off) button on any of the room units
is pressed.
Show room unit ID at controller power up
Disabled:
The room units do not indicate their room unit IDs at controller power up
(default setting).
Enabled:
The room units indicate their room unit IDs at controller power up.
For room units without display, the LED in the centre of the room unit blinks. One slow
blink indicates ID 1 and two fast blinks indicate ID 2.
For room units with display, ID 1 and ID 2 are shown in the displays.
When the indications are shown in room units with display, the IDs can be swapped
between the room units by pressing the up or down button on any of the room units.
The indications are shown for 1 minute or until the occupancy (on/off) button on any of
the room units is pressed.
Search for and identify room units
Disabled:
No search is performed (default setting).
Enabled:
The controller initiates a search for and identification of the room units that
are connected to the controller.
Swap room unit IDs
Disabled:
The room unit IDs are not swapped (default setting).
Enabled:
The room unit IDs are swapped between the room units.
3.9.3
Max setpoint adjustment
This section describes the max setpoint adjustment configuration settings.
Table 3-7 Max setpoint adjustment configuration settings.
Configuration setting
Description
Max setpoint adjustment up (°C)
Specifies the maximum allowed setpoint adjustment up.
Max setpoint adjustment down (°C)
Specifies the maximum allowed setpoint adjustment down.
3.9.4
Display
This section describes the display configuration settings.