Signal name
Object name
Instance
number
Writeable Description
RCPActual.
RegioExerciseOnHeat1Zone2
RegioExerciseOnHeat1-
Zone2
20090
NO
Valve Heat 1 in exercise
RCPActual.
RegioExerciseOnHeat2Zone2
RegioExerciseOnHeat2-
Zone2
20091
NO
Valve Heat 2 in exercise
RCPActual.
RegioExerciseOnCool1Zone2
RegioExerciseOnCool1-
Zone2
20092
NO
Valve Cool 1 in exercise
RCPActual.
RegioExerciseOnCool2Zone2
RegioExerciseOnCool2-
Zone2
20093
NO
Not used
RCPActual.
RegioExerciseOnHeatCoolZone2
RegioExerciseOnHeat-
CoolZone2
20094
NO
Valve HeatCool in exercise
RCPActual.
RegioDIOpenWindowCombined
RegioDIOpenWindow-
Combined
20095
NO
Open window indication all Controllers
RCPActual.
RegioDICondenseAlarmCombined
RegioDICondenseAlarm-
Combined
20096
NO
Alarm Condens indication all Controllers
RCPActual.
RegioDIPresenceCombined
RegioDIPresenceCom-
bined
20097
NO
Pressens indication all Controllers (This is
the combination of all pins not actualy the
presence state)
RCPActual.
RegioDIChangeoverCombined
RegioDIChangeoverCom-
bined
20098
NO
Change over indication all Controllers
D.3 Analog values
Signal name
Object name
Instance
number
Writeable Description
RCPSettings.
RegioHeatSetPointOccupied
RegioHeatSetPointOccu-
pied
30001
YES
Room Base setpoint heating
RCPSettings.
RegioCoolSetPointOccupied
RegioCoolSetPointOccu-
pied
30002
YES
Room Base setpoint cooling
RCPSettings.
RegioRoomTempPBand
RegioRoomTempPBand
30003
YES
Temperature PID P Band
RCPSettings.
RegioRoomTempITime
RegioRoomTempITime
30004
YES
Temperature PID I Time
RCPSettings.
RegioHeatSetPointUnoccupied
RegioHeatSetPointUnoc-
cupied
30005
YES
Setpoint heating in Unoccupied
RCPSettings.
RegioCoolSetPointUnoccupied
RegioCoolSetPointUnoc-
cupied
30006
YES
Setpoint Cooling in Unoccupied
RCPSettings.
RegioSetPointDeadBandStandby
RegioSetPointDeadBand-
Standby
30007
YES
Deadband in Standby mode
RCPSettings.
RegioFrostProtectionSetPoint
RegioFrostProtectionSet-
Point
30008
YES
Setpoint frostprotection
RCPSettings.
RegioSetPOffsetRemote
RegioSetPOffsetRemote
30009
YES
Setpoint Offset Remote
RCPSettings.
RegioControllerStateBypassTime
RegioControllerStateBy-
passTime
30011
YES
Time for Bypass mode (Min)
RCPSettings.
RegioVAVOutputMinLimitOff
RegioVAVOutputMinLi-
mitOff
30012
YES
Min Limit for VAV Output at off State
RCPSettings.
RegioVAVOutputMinLimitUno
RegioVAVOutputMinLimi-
tUno
30013
YES
Min Limit for VAV Output at Unoccupied
State
RCPSettings.
RegioVAVOutputMinLimitStandby
RegioVAVOutputMinLimit-
Standby
30014
YES
Min Limit for VAV Output at Stanby State
RCPSettings.
RegioVAVOutputMinLimitOcc
RegioVAVOutputMinLimi-
tOcc
30015
YES
Min Limit for VAV Output at Occupied or
Bypass State
126
Regio
Ardo
manual, Rev. D