Signal name
Modbus
address
Scale
Description
RCPActual.RegioCoolSeq1Zone2
46
1
Control valve Cooling 1 Room2
RCPActual.RegioCoolSeq2Zone2
47
1
Not used
RCPActual.RegioHeatCoolOutputZone2
48
1
Control valve Heating/Cooling Room2
RCPActual.RegioVAVOutputZone2
49
1
Control VAV damper Room2
RCPActual.RegioECFanOutputZone2
50
1
Control EC Fan Room2
RCPActual.RegioRoomTempZone2
51
10
Roomtemp internal or external
RCPActual.RegioPIDOutputZone2
52
1
Controller output Room2
RCPActual.RegioControlStateZone2
53
1
Current unit state Room2:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
4=ByPass
RCPActual.RegioHeatCoolSymbolZone2
54
1
Current controller state Room2:
0=Off,
1=Heating
2=Cooling
3=Heating and Cooling
RCPActual.RegioPIDSetPZone2
55
10
Setpoint Sent to PID Room2
RCPActual.RegioSetPAdjustmentZone2
56
10
Setpoint Adjustment for Room2
RCPActual.RegioHeatOutputZone2
57
1
Control signal Heating 0-100 % Room2
RCPActual.RegioCoolOutputZone2
58
1
Control signal Cooling 0-100 % Room2
RCPActual.RegioVAVOutputSignalZone2
59
1
Control signal VAV 0-100% Room2
RCPActual.RegioECFanOutputSignalZone2
60
1
Control signal EC fan 0-100% Room2
RCPActual.RegioFanSpeedZone2
61
1
Current 3speed fan speed Room2:
0=Off
1=Speed1
2=Speed2
3=Speed3
RCPActual.RegioECFanSpeedIndexZone2
62
1
Current EC fan speed converted to index, used in RU
Room2:
0=Off
1=Speed1
2=Speed2
3=Speed3
RCPActual.RegioFanSpeedSelectCombinedZone2 63
1
Fan speed Selected Room2:
0=Off
1=Speed1
2=Speed2
3=Speed3
4=Auto
RCPActual.RegioByPassRunMinZone2
64
1
Time left in ByPass mode (min) Room2
RCPActual.RegioRoomTempAverage
65
10
Average Roomtemp internal or external
RCPActual.RegioAIChangeOverAverage
66
10
Average Change over Temperature
RCPActual.RegioOutDoorTempAverage
67
10
Average Temperature from all controllers
RCPActual.RegioCondenseAverage
68
1
Condense Average
RCPActual.RegioRoomCO2Average
69
1
Average CO2 from all controllers
RCPActual.RegioRoomRHAverage
70
1
Average Humidity from all controllers
RCPActual.RegioSupplyAirTempAverage
71
10
SupplyAir Temperature from all controllers
RCPActual.RegioSetpointOffsetCombined
72
10
Setpoint OffSet , last changed offset from all controllers
Regio
Ardo
manual, Rev. D
97