Signal name
Modbus
address
Default
value
Description
RCPSettings.Regio3PointValveStopSignal
25
0
If enabled it will stop the output digital signal when full
open/close. The signal will stop after 1 minute of full open/
close time. This option is applied to all 3 point valves in this
system.
RCPSettings.RegioPropValveHeat1NCNO
26
0
Output Type (NC/NO) if puls prop control valves
RCPSettings.RegioPropValveHeat2NCNO
27
0
Output Type (NC/NO) if puls prop control valves
RCPSettings.RegioPropValveCool1NCNO
28
0
Output Type (NC/NO) if puls prop control valves
RCPSettings.RegioPropValveCool2NCNO
29
0
Not used
RCPSettings.RegioPropValveHeatCoolNCNO
30
0
Output Type (NC/NO) if puls prop control valves
RCPSettings.RegioPropValveVAVNCNO
31
0
Output Type (NC/NO) if puls prop control valves
RCPSettings.RegioPropValveECFanCNO
32
0
Output Type (NC/NO) if puls prop control valves
RCPSettings.RegioPropValveHeat1NCNOZone2
33
0
Output Type (NC/NO) if puls prop control valves Room2
RCPSettings.RegioPropValveHeat2NCNOZone2
34
0
Output Type (NC/NO) if puls prop control valves Room2
RCPSettings.RegioPropValveCool1NCNOZone2
35
0
Output Type (NC/NO) if puls prop control valves Room2
RCPSettings.RegioPropValveCool2NCNOZone2
36
0
Not used
RCPSettings.
RegioPropValveHeatCoolNCNOZone2
37
0
Output Type (NC/NO) if puls prop control valves Room2
RCPSettings.RegioPropValveVAVNCNOZone2
38
0
Output Type (NC/NO) if puls prop control valves Room2
RCPSettings.RegioPropValveECFanCNOZone2
39
0
Output Type (NC/NO) if puls prop control valves Room2
RCPSettings.RegioSixWayValveSequenceOrder
40
0
6-Way Valve Sequence Order:
0=Heat 1st Sequence
1=Heat 2nd Sequence
RCPSettings.
RegioSixWayValveSequenceOrderZone2
41
0
6-Way Valve Sequence Order Room2:
0=Heat 1st Sequence
1=Heat 2nd Sequence
RCPSettings.RegioDi1NC
42
0
Digital input 1 function :
0=Normaly open
1=normaly closed
RCPSettings.RegioDi2NC
43
0
Digital input 2 function
RCPSettings.RegioDi3NC
44
0
Digital input 3 function
RCPSettings.RegioDi4NC
45
0
Digital input 4 function
RCPSettings.RegioRUConfigMenuDisable
48
0
Enable entering the configuration menu in the RU unit
when pressing the UP and Down Key
RCPSettings.RegioUseRemoteValues
49
1
If 1 it will show in the RU the network avalues from the
master controller(All controllers Average) if 0 will display
i'ts own room temperature
RCPSettings.RegioRUConfigMenuDisableZone2
50
0
Enable entering the configuration menu in the RU unit
when pressing the UP and Down Key
RCPSettings.RegioUseRemoteValuesZone2
51
1
If 1 it will show in the RU the network avalues from the
master controller(All controllers Average) if 0 will display
i'ts own room temperature
RCPSettings.RegioForceDisplayID
52
0
Forces the Display to identify themselves(show number on
display/blink leds), can leave this state by pressing On/Off
button
RCPSettings.RegioDisplayIDOnPowerUp
53
0
If enabled will show display identification on power for 60
seconds or press of the on/off button
RCPSettings.RegioForceDisplaySearch
54
0
Trigger a search for display on display port
RCPSettings.RegioSwapDisplayAddress
55
0
Swap the addres of the display. RU in Room1 will go to
Room2 and ViceVersa. Only possible with two display
detected and Dual Zone Active
RCPSettings.RegioDisable2ndSequence
56
0
If enabled when Condensation input is active in modes with
2 sequences the 2nd sequence will also be set to 0%
Regio
Ardo
manual, Rev. D
93