Controller connections and wiring diagrams
Table 7-1 Controller connection descriptions.
Terminal № and
designator
Type
Description
1 G
Supply voltage
24 V AC supply voltage.
2 G0
Supply voltage (reference)
24 V AC supply voltage (reference).
Ground
Earth ground.
10 GDO
14 GDO
Supply voltage output
24 V AC supply voltage output for use together with digital outputs.
11 DO1b
12 DO2b
13 DO3b
15 DO4b
16 DO5b
17 DO6b
Digital output
Mosfet output used for valve, 3-speed fan, blinds, or lighting control, or for
alarms or forced ventilation.
20 Agnd
23 Agnd
30 Agnd
45 Agnd
Analog ground
Signal ground for analog inputs and outputs.
21 AI1a
22 AI2a
24 AI3a
25 AI4a
Analog input
Input used for change-over detection or for temperature, CO
2
, condensation,
or relative humidity sensor.
31 CI1a
32 CI2a
Condensation input
Input dedicated for Regin’s condensation detector KG-A/1.
Ethernet communication port
8P8C modular connector used for Ethernet - TCP/IP communication.
40 AO1a
41 AO2a
42 AO3a
43 AO4a
Analog output
Output used for valve, damper, or EC fan control.
50 GND
53 GND
Digital ground
Signal ground for digital inputs.
51 DI1b
52 DI2b
54 DI3b
55 DI4b
Digital input
Input used for presence, open window, or change-over detection.
Ext. Disp.
External display communica-
tion port
4P4C modular connector used for communication with an ED-RU... room unit.
60 E
61 N
62 A
63 B
RS485 communication port
RS485 connector used for communication via BACnet, or for master/slave
communication via Exoline or Modbus.
N can be used as common signal reference if a large difference in potential
between units in the network is causing communication problems.
This connection is not galvanically isolated.
70 E
71 N
72 A
73 B
RS485 communication port
RS485 connector used for communication via BACnet, or for master/slave
communication via Exoline or Modbus.
N can be used as common signal reference if a large difference in potential
between units in the network is causing communication problems.
This connection is galvanically isolated.
Regio
Ardo
manual, Rev. D