Signal name
Object name
Instance
number
Writeable Description
RCPActual.
RegioOutDoorTempZone2
RegioOutDoorTempZone2 40041
NO
Outdoor temp Room2
RCPActual.
RegioCondensationZone2
RegioCondensationZone2 40042
NO
Condense Room2
RCPActual.RegioRoomCO2Zone2
RegioRoomCO2Zone2
40043
NO
Room CO2 Room2
RCPActual.RegioRoomRHZone2
RegioRoomRHZone2
40044
NO
Room RH Room2
RCPActual.
RegioSupplyAirTempZone2
RegioSupplyAirTemp-
Zone2
40045
NO
SupplyAir Temperature Room2
RCPActual.RegioHeatSeq1Zone2
RegioHeatSeq1Zone2
40046
NO
Control valve Heating 1 Room2
RCPActual.RegioHeatSeq2Zone2
RegioHeatSeq2Zone2
40047
NO
Control valve Heating 2 Room2
RCPActual.RegioCoolSeq1Zone2
RegioCoolSeq1Zone2
40048
NO
Control valve Cooling 1 Room2
RCPActual.RegioCoolSeq2Zone2
RegioCoolSeq2Zone2
40049
NO
Not used
RCPActual.
RegioHeatCoolOutputZone2
RegioHeatCoolOutput-
Zone2
40050
NO
Control valve Heating/Cooling Room2
RCPActual.RegioVAVOutputZone2
RegioVAVOutputZone2
40051
NO
Control VAV damper Room2
RCPActual.
RegioECFanOutputZone2
RegioECFanOutputZone2 40052
NO
Control EC Fan Zone2
RCPActual.RegioRoomTempZone2 RegioRoomTempZone2
40053
NO
Roomtemp internal or external
RCPActual.RegioPIDOutputZone2
RegioPIDOutputZone2
40054
NO
Controller output Room2
RCPActual.RegioPIDSetPZone2
RegioPIDSetPZone2
40057
NO
Setpoint Sent to PID Room2
RCPActual.
RegioSetPAdjustmentZone2
RegioSetPAdjustment-
Zone2
40058
NO
Setpoint Adjustment for Room2
RCPActual.RegioHeatOutputZone2 RegioHeatOutputZone2
40059
NO
Control signal Heating 0-100 % Room2
RCPActual.RegioCoolOutputZone2 RegioCoolOutputZone2
40060
NO
Control signal Cooling 0-100 % Room2
RCPActual.
RegioVAVOutputSignalZone2
RegioVAVOutputSignal-
Zone2
40061
NO
Control signal VAV 0-100% Room2
RCPActual.
RegioECFanOutputSignalZone2
RegioECFanOutputSignal-
Zone2
40062
NO
Control signal EC fan 0-100% Room2
RCPActual.
RegioECFanSpeedIndexZone2
RegioECFanSpeedIndex-
Zone2
40064
NO
Current EC fan speed converted to index 1=
Off, 2=Speed1, 3=Speed2, 4=Speed3 used
in RU Room2
RCPActual.
RegioByPassRunMinZone2
RegioByPassRunMin-
Zone2
40066
NO
Time left in ByPass mode (min) Room2
RCPActual.
RegioRoomTempAverage
RegioRoomTempAverage
40067
NO
Average Roomtemp internal or external
RCPActual.
RegioAIChangeOverAverage
RegioAIChangeOverA-
verage
40068
NO
Average Change over Temperature
RCPActual.
RegioOutDoorTempAverage
RegioOutDoorTempA-
verage
40069
NO
Average Temperature from all controllers
RCPActual.RegioCondenseAverage RegioCondenseAverage
40070
NO
Condense Average
RCPActual.
RegioRoomCO2Average
RegioRoomCO2Average
40071
NO
Average CO2 from all controllers
RCPActual.RegioRoomRHAverage
RegioRoomRHAverage
40072
NO
Average Humidity from all controllers
RCPActual.
RegioSupplyAirTempAverage
RegioSupplyAirTempA-
verage
40073
NO
SupplyAir Temperature from all controllers
RCPActual.
RegioSetpointOffsetCombined
RegioSetpointOffsetCom-
bined
40074
NO
Setpoint OffSet , last changed offset from all
controllers
AlaData.AlaPt1_DelayValue
AlaPt1_DelayValue
30172
YES
Delay value for point no. 1 Condensation
AlaData.AlaPt2_DelayValue
AlaPt2_DelayValue
30173
YES
Delay value for point no. 2
CondensationZone2
AlaData.AlaPt3_DelayValue
AlaPt3_DelayValue
30174
YES
Delay value for point no. 3 SensorAlarm
Regio
Ardo
manual, Rev. D
131