Signal name
Object name
Instance
number
Writeable Description
RCPSettings.
RegioHeat1OutputManual
RegioHeat1OutputManual 30092
YES
Manual value Heat 1
RCPSettings.
RegioHeat2OutputManual
RegioHeat2OutputManual 30093
YES
Manual value Heat 2
RCPSettings.
RegioCoolOutputManual
RegioCoolOutputManual
30094
YES
Manual value Cool
RCPSettings.
RegioHeatCoolOutputManual
RegioHeatCoolOutputMa-
nual
30095
YES
Manual value Heat Cool
RCPSettings.
RegioVAVOutputManual
RegioVAVOutputManual
30096
YES
Manual value VAV
RCPSettings.
RegioECFanOutputManual
RegioECFanOutputMa-
nual
30097
YES
Manual value ECFan
RCPSettings.
RegioHeat1OutputManualZone2
RegioHeat1OutputManual-
Zone2
30098
YES
Manual value Heat 1 Room2
RCPSettings.
RegioHeat2OutputManualZone2
RegioHeat2OutputManual-
Zone2
30099
YES
Manual value Heat 2 Room2
RCPSettings.
RegioCoolOutputManualZone2
RegioCoolOutputManual-
Zone2
30100
YES
Manual value Cool Room2
RCPSettings.
RegioHeatCoolOutputManualZone2
RegioHeatCoolOutputMa-
nualZone2
30101
YES
Manual value Heat Cool Room2
RCPSettings.
RegioVAVOutputManualZone2
RegioVAVOutputManual-
Zone2
30102
YES
Manual value VAV Room2
RCPSettings.
RegioECFanOutputManualZone2
RegioECFanOutputMa-
nualZone2
30103
YES
Manual value ECFan Room2
RCPSettings.RegioRUButtonsUsed RegioRUButtonsUsed
30121
YES
Buttons that can be used in the RU
RCPSettings.
RegioRUTemperatureCompZone2
RegioRUTemperature-
CompZone2
30122
YES
Temperature Compensation for RU 2
RCPSettings.
RegioRUButtonsUsedZone2
RegioRUButtonsUsed-
Zone2
30123
YES
Buttons that can be used in the RU
RCPSettings.RegioAlarmHyst
RegioAlarmHyst
30124
YES
Alarm hysteresis
RCPSettings.
RegioRoomTempHighLimit
RegioRoomTempHighLimit 30125
YES
High room temp
RCPSettings.
RegioRoomTempLowLimit
RegioRoomTempLowLimit 30126
YES
Low room temp
RCPSettings.
RegioRoomTempMaxDeviationLimit
RegioRoomTempMaxDe-
viationLimit
30127
YES
Max allowed difference between setpoint
and room temp before alarm
RCPSettings.
RegioAlarmHystZone2
RegioAlarmHystZone2
30128
YES
Alarm hysteresis Room2
RCPSettings.
RegioRoomTempHighLimitZone2
RegioRoomTempHighLi-
mitZone2
30129
YES
High room temp Room2
RCPSettings.
RegioRoomTempLowLimitZone2
RegioRoomTempLowLi-
mitZone2
30130
YES
Low room temp Room2
RCPSettings.RegioRoomTempMax-
DeviationLimitZone2
RegioRoomTempMaxDe-
viationLimitZone2
30131
YES
Max allowed difference between setpoint
and room temp before alarm Room2
RCPSettings.RegioCondenseLimit
RegioCondenseLimit
30132
YES
High limit for condense alarm
RCPSettings.RegioCondenseHyst
RegioCondenseHyst
30133
YES
Condense alarm hysteresis
RCPSettings.
RegioCondenseLimitZone2
RegioCondenseLimit-
Zone2
30134
YES
High limit for condense alarm Room2
RCPSettings.
RegioCondenseHystZone2
RegioCondenseHyst-
Zone2
30135
YES
Condense alarm hysteresis Room2
RCPSettings.RegioCO2MaxLimit
RegioCO2MaxLimit
30136
YES
Max CO2 Level for Alarm
RCPSettings.
RegioCO2MaxLimitZone2
RegioCO2MaxLimitZone2 30137
YES
Max CO2 Level for Alarm Room2
Regio
Ardo
manual, Rev. D
129