Signal name
Object name
Instance
number
Writeable Description
RCPSettings.
RegioVAVOutputMaxLimitZone2
RegioVAVOutputMaxLimit-
Zone2
30048
YES
Max Limit for VAV Output Room2
RCPSettings.RegioSupplyAirTem-
pLimCascadeFactorZone2
RegioSupplyAirTempLim-
CascadeFactorZone2
30049
YES
Cascade Factor for the Cascade PID
Room2
RCPSettings.RegioSupplyAirTem-
pLimHeatMinLimitZone2
RegioSupplyAirTempLim-
HeatMinLimitZone2
30050
YES
Min Setpoint for the Cascade PID in Heat
Mode Room2
RCPSettings.RegioSupplyAirTem-
pLimHeatMaxLimitZone2
RegioSupplyAirTempLim-
HeatMaxLimitZone2
30051
YES
Max Setpoint for the Cascade PID in Heat
Mode Room2
RCPSettings.RegioSupplyAirTem-
pLimCoolMinLimitZone2
RegioSupplyAirTempLim-
CoolMinLimitZone2
30052
YES
Min Setpoint for the Cascade PID in Cool
Mode Room2
RCPSettings.RegioSupplyAirTem-
pLimCoolMaxLimitZone2
RegioSupplyAirTempLim-
CoolMaxLimitZone2
30053
YES
Max Setpoint for the Cascade PID in Cool
Mode Room2
RCPSettings.RegioSupplyAirTem-
pLimFrostProtSetPointZone2
RegioSupplyAirTempLim-
FrostProtSetPointZone2
30054
YES
Supply Air Temp Frost Protection Tempera-
ture Room2
RCPSettings.
RegioCO2PBandZone2
RegioCO2PBandZone2
30055
YES
CO2 PID P Gain Room2
RCPSettings.RegioCO2ITimeZone2 RegioCO2ITimeZone2
30056
YES
CO2 PID I Time Room2
RCPSettings.
RegioCO2SetpointZone2
RegioCO2SetpointZone2
30057
YES
Setpoint for CO2 PI Controller in PPM
Room2
RCPSettings.
RegioFanStopTimeZone2
RegioFanStopTimeZone2
30058
YES
Time (Sec) for the Fan Stop delay when Fan
AfterBlow used
RCPSettings.
RegioCVHeatExerciseDay
RegioCVHeatExerciseDay 30062
YES
Day for exercise heating and heat/cool
valve, 1=Never, 2-8=mon-sun, 9=every day
RCPSettings.
RegioCVCoolExerciseDay
RegioCVCoolExerciseDay 30063
YES
Day for exercise cooling valve
RCPSettings.
RegioCVHeatExerciseHour
RegioCVHeatExercise-
Hour
30064
YES
Hour for exercise heating and heat/cool
valve
RCPSettings.
RegioCVCoolExerciseHour
RegioCVCoolExercise-
Hour
30065
YES
Hour for exercise cooling valve
RCPSettings.
RegioHeatExerciseTime
RegioHeatExerciseTime
30066
YES
Time in seconds to Exercise the Heat
Valves
RCPSettings.
RegioCoolExerciseTime
RegioCoolExerciseTime
30067
YES
Time in seconds to Exercise the Cool Valves
RCPSettings.
RegioCVHeatExerciseDayZone2
RegioCVHeatExercise-
DayZone2
30068
YES
Day for exercise heating valve Room2, 1=
Never, 2-8=mon-sun, 9=every day
RCPSettings.
RegioCVCoolExerciseDayZone2
RegioCVCoolExercise-
DayZone2
30069
YES
Day for exercise cooling valve Room2
RCPSettings.
RegioCVHeatExerciseHourZone2
RegioCVHeatExercise-
HourZone2
30070
YES
Hour for exercise heating valve Room2
RCPSettings.
RegioCVCoolExerciseHourZone2
RegioCVCoolExercise-
HourZone2
30071
YES
Hour for exercise cooling valve Room2
RCPSettings.
RegioHeatExerciseTimeZone2
RegioHeatExerciseTime-
Zone2
30072
YES
Time in seconds to Exercise the Heat
Valves for Room2
RCPSettings.
RegioCoolExerciseTimeZone2
RegioCoolExerciseTime-
Zone2
30073
YES
Time in seconds to Exercise the Cool Valves
for Room2
RCPSettings.RegioAi1Comp
RegioAi1Comp
30074
YES
Analog input 1 compensation
RCPSettings.RegioAi2Comp
RegioAi2Comp
30075
YES
Analog input 2 compensation
RCPSettings.RegioAi3Comp
RegioAi3Comp
30076
YES
Analog input 3 compensation
RCPSettings.RegioAi4Comp
RegioAi4Comp
30077
YES
Analog input 4 compensation
RCPSettings.
RegioInternalTempComp
RegioInternalTempComp
30078
YES
Internal temperature sensor compensation
RCPSettings.
RegioInternalTempCompZone2
RegioInternalTempComp-
Zone2
30079
YES
Internal temperature sensor compensation
for Room2
128
Regio
Ardo
manual, Rev. D