Signal name
Object name
Instance
number
Writeable Description
RCPSettings.
RegioVAVOutputMaxLimit
RegioVAVOutputMaxLimit
30016
YES
Max Limit for VAV Output
RCPSettings.
RegioChangeOverAIDiffHeat
RegioChangeOverAIDiff-
Heat
30018
YES
The difference between the temperature in
the room and the media temperature for
change over to cooling
RCPSettings.
RegioChangeOverAIDiffCool
RegioChangeOverAIDiff-
Cool
30019
YES
The difference between the temperature in
the room and the media temperature for
change over to heating
RCPSettings.RegioSupplyAirTem-
pLimCascadeFactor
RegioSupplyAirTempLim-
CascadeFactor
30020
YES
Cascade Factor for the Cascade PID
RCPSettings.RegioSupplyAirTem-
pLimHeatMinLimit
RegioSupplyAirTempLim-
HeatMinLimit
30021
YES
Min Setpoint for the Cascade PID in Heat
Mode
RCPSettings.RegioSupplyAirTem-
pLimHeatMaxLimit
RegioSupplyAirTempLim-
HeatMaxLimit
30022
YES
Max Setpoint for the Cascade PID in Heat
Mode
RCPSettings.RegioSupplyAirTem-
pLimCoolMinLimit
RegioSupplyAirTempLim-
CoolMinLimit
30023
YES
Min Setpoint for the Cascade PID in Cool
Mode
RCPSettings.RegioSupplyAirTem-
pLimCoolMaxLimit
RegioSupplyAirTempLim-
CoolMaxLimit
30024
YES
Max Setpoint for the Cascade PID in Cool
Mode
RCPSettings.RegioSupplyAirTem-
pLimFrostProtSetPoint
RegioSupplyAirTempLim-
FrostProtSetPoint
30025
YES
Supply Air Temp Frost Protection
Temperature
RCPSettings.RegioCO2PBand
RegioCO2PBand
30026
YES
CO2 PID P Band
RCPSettings.RegioCO2ITime
RegioCO2ITime
30027
YES
CO2 PID I Time
RCPSettings.RegioCO2SetPoint
RegioCO2SetPoint
30028
YES
Setpoint for CO2 PI Controller in PPM
RCPSettings.RegioFanStopTime
RegioFanStopTime
30029
YES
Time (Sec) for the Fan Stop delay when Fan
AfterBlow used
RCPSettings.
RegioHeatSetPointOccupiedZone2
RegioHeatSetPointOccu-
piedZone2
30033
YES
Room Base setpoint heating Room2
RCPSettings.
RegioCoolSetPointOccupiedZone2
RegioCoolSetPointOccu-
piedZone2
30034
YES
Room Base setpoint cooling Room2
RCPSettings.
RegioRoomTempPBandZone2
RegioRoomTempPBand-
Zone2
30035
YES
Temperature PID P Band Room2
RCPSettings.
RegioRoomTempITimeZone2
RegioRoomTempITime-
Zone2
30036
YES
Temperature PID I Time Room2
RCPSettings.RegioHeatSetPointU-
noccupiedZone2
RegioHeatSetPointUnoc-
cupiedZone2
30037
YES
Setpoint heating in Unoccupied Room2
RCPSettings.RegioCoolSetPointU-
noccupiedZone2
RegioCoolSetPointUnoc-
cupiedZone2
30038
YES
Setpoint Cooling in Unoccupied Room2
RCPSettings.RegioSetPointDead-
BandStandbyZone2
RegioSetPointDeadBand-
StandbyZone2
30039
YES
Deadband in Standby mode Room2
RCPSettings.
RegioFrostProtectionSetPointZone2
RegioFrostProtectionSet-
PointZone2
30040
YES
Setpoint frostprotection Room2
RCPSettings.
RegioSetPOffsetRemoteZone2
RegioSetPOffsetRemote-
Zone2
30041
YES
Remote Setpoint Offset Room2
RCPSettings.RegioControllerState-
BypassTimeZone2
RegioControllerStateBy-
passTimeZone2
30043
YES
Time for Bypass mode (Min) Room2
RCPSettings.
RegioVAVOutputMinLimitOffZone2
RegioVAVOutputMinLimi-
tOffZone2
30044
YES
Min Limit for VAV Output at off State Room2
RCPSettings.
RegioVAVOutputMinLimitUnoZone2
RegioVAVOutputMinLimi-
tUnoZone2
30045
YES
Min Limit for VAV Output at Unoccupied
State Room2
RCPSettings.RegioVAVOutputMin-
LimitStandbyZone2
RegioVAVOutputMinLimit-
StandbyZone2
30046
YES
Min Limit for VAV Output at Stanby State
Room2
RCPSettings.
RegioVAVOutputMinLimitOccZone2
RegioVAVOutputMinLimi-
tOccZone2
30047
YES
Min Limit for VAV Output at Occupied or
Bypass State Room2
Regio
Ardo