Signal name
Object name
Instance
number
Writeable Description
RCPSettings.
RegioLightManualZone2
RegioLightManualZone2
10003
YES
Controls the light when central control
Room2
RCPSettings.
RegioLightingCmdRemoteZone2
RegioLightingCmdRemo-
teZone2
10004
YES
Remote Light Control Room2
RCPSettings.
RegioRUConfigMenuDisable
RegioRUConfigMenuDis-
able
10005
YES
Enable entering the configuration menu in
the RU unit when pressing the UP and
Down Key
RCPSettings.
RegioRUConfigMenuDisableZone2
RegioRUConfigMenuDisa-
bleZone2
10006
YES
Enable entering the configuration menu in
the RU unit when pressing the UP and
Down Key
RCPSettings.RegioForceDisplayID
RegioForceDisplayID
10007
YES
Forces the Display to identify themselves
(show number on display/blink leds), can
leave this state by pressing On/Off button
RCPSettings.
RegioAutoSummerTime
RegioAutoSummerTime
10008
YES
Switch automaticly between summer and
winter time
RCPActual.RegioOpenWindowInd
RegioOpenWindowInd
20001
NO
Open window indication
RCPActual.
RegioCondensationAlarm
RegioCondensationAlarm
20002
NO
Alarm Condensation indication
RCPActual.RegioPresenceInd
RegioPresenceInd
20003
NO
Pressens indication
RCPActual.RegioChangeOverInd
RegioChangeOverInd
20004
NO
Change over indication
RCPActual.RegioDigOut1
RegioDigOut1
20005
NO
Digital output 1
RCPActual.RegioDigOut2
RegioDigOut2
20006
NO
Digital output 2
RCPActual.RegioDigOut3
RegioDigOut3
20007
NO
Digital output 3
RCPActual.RegioDigOut4
RegioDigOut4
20008
NO
Digital output 4
RCPActual.RegioFanSpeed1Output RegioFanSpeed1Output
20011
NO
Start Fan Speed 1
RCPActual.RegioFanSpeed2Output RegioFanSpeed2Output
20012
NO
Start Fan Speed 2
RCPActual.RegioFanSpeed3Output RegioFanSpeed3Output
20013
NO
Start Fan Speed 3
RCPActual.RegioLightingOutput
RegioLightingOutput
20014
NO
Start signal Lighting
RCPActual.
RegioSunBlindsInOutput
RegioSunBlindsInOutput
20015
NO
In signal Blind
RCPActual.
RegioSunBlindsOutOutput
RegioSunBlindsOutOutput 20016
NO
Out signal Blind
RCPActual.RegioForcedVentOutput RegioForcedVentOutput
20017
NO
Start forced ventilation
RCPActual.RegioHeat1IncOutput
RegioHeat1IncOutput
20018
NO
Increase heat 1 valve
RCPActual.RegioHeat1DecOutput
RegioHeat1DecOutput
20019
NO
Decrease heat 1 valve
RCPActual.
RegioHeat1PulsPropOutput
RegioHeat1PulsPro-
pOutput
20020
NO
Puls prop heat 1 valve
RCPActual.RegioHeat2IncOutput
RegioHeat2IncOutput
20021
NO
Increase heat 2 valve
RCPActual.RegioHeat2DecOutput
RegioHeat2DecOutput
20022
NO
Decrease heat 2 valve
RCPActual.
RegioHeat2PulsPropOutput
RegioHeat2PulsPro-
pOutput
20023
NO
Puls prop heat 2 valve
RCPActual.RegioCool1IncOutput
RegioCool1IncOutput
20024
NO
Increase cool 1 valve
RCPActual.RegioCool1DecOutput
RegioCool1DecOutput
20025
NO
Decrease cool 1 valve
RCPActual.
RegioCool1PulsPropOutput
RegioCool1PulsPro-
pOutput
20026
NO
Puls prop cool 1 valve
RCPActual.RegioCool2IncOutput
RegioCool2IncOutput
20027
NO
Not used
RCPActual.RegioCool2DecOutput
RegioCool2DecOutput
20028
NO
Not used
RCPActual.
RegioCool2PulsPropOutput
RegioCool2PulsPro-
pOutput
20029
NO
Not used
Regio
Ardo
manual, Rev. D
123