Maximum and minimum limits for the output signal can be set, see section
Table 2-5 Controller output configuration values and controller output types.
Output signal
Controller output configuration value
Controller output type
Y1
Change-over valve
Analog
Change-over valve, increase
Change-over valve, decrease
Digital
Digital
Change-over valve, thermal (PWM)
Digital
illustrates the control behaviour in heating mode, and when no maximum or minimum limits are
set.
The heating demand increases as the room temperature falls. When the room temperature falls below the
heating setpoint,
Y1: Change-over (heating mode) signal
increases to respond to the heating demand. At 100%
heating demand,
Y1: Change-over (heating mode) signal
reaches its maximum.
When the room temperature is higher than the heating setpoint and no heating demand exists,
Y1: Change-
over (heating mode) signal
is at its minimum.
Figure 2-6 Control behaviour for the Heating/Cooling (change-over) controller mode when the controller is in heating
mode.
illustrates the control behaviour in cooling mode, and when no maximum or minimum limits are
set.
The cooling demand increases as the room temperature rises. When the room temperature rises above the
cooling setpoint,
Y1: Change-over (cooling mode) signal
increases to respond to the cooling demand. At 100%
cooling demand,
Y1: Change-over (cooling mode) signal
reaches its maximum.
When the room temperature is lower than the cooling setpoint and no cooling demand exists,
Y1: Change-
over (cooling mode) signal
is at its minimum.
Y1: Change-over valve (heating mode) signal
Output
Max: 100%
Heating
setpoint
Min: 0%
Room temperature
100%
0%
Heating demand
12
Regio
Ardo
manual, Rev. D