Signal name
Modbus
address
Description
RCPActual.RegioHeat2DecOutputZone2
60
Decrease heat 2 valve Room2
RCPActual.RegioHeat2PulsPropOutputZone2
61
Puls prop heat 2 valve Room2
RCPActual.RegioCool1IncOutputZone2
62
Increase cool 1 valve Room2
RCPActual.RegioCool1DecOutputZone2
63
Decrease cool 1 valve Room2
RCPActual.RegioCool1PulsPropOutputZone2
64
Puls prop cool 1 valve Room2
RCPActual.RegioCool2IncOutputZone2
65
Not used
RCPActual.RegioCool2DecOutputZone2
66
Not used
RCPActual.RegioCool2PulsPropOutputZone2
67
Not used
RCPActual.RegioHeatCoolIncOutputZone2
68
Increase Heat cool valve Room2
RCPActual.RegioHeatCoolDecOutputZone2
69
Decrease Heat cool valve Room2
RCPActual.RegioHeatCoolPulsPropOutputZone2 70
Puls prop Heat cool valve Room2
RCPActual.RegioSumAlarmZone2
71
Sum alarm
RCPActual.RegioSumAlarmAZone2
72
Sum alarm A
RCPActual.RegioSumAlarmBZone2
73
Sum alarm B
RCPActual.RegioPIDAlaManualZone2
74
Alarm Output: The Regulator is in Manual mode Room2
RCPActual.RegioRoomTempControlStateZone2
75
Current controller state Room2:
0=Heating
1=Cooling
RCPActual.RegioSunBlindsStateZone2
76
Blind Position Room2:
0=In
1=Out
RCPActual.RegioPresenceZone2
77
Presence indication Room2
RCPActual.RegioCO2PresenceZone2
78
Is set if presence if CO2 is high Room2
RCPActual.RegioAIChangeOverStateZone2
79
Is set if change over from analog input Room2
RCPActual.RegioChangeOverStateZone2
80
Is set if change over Room2
RCPActual.RegioRoomTempSensorAlarmZone2 81
Is set if sensor alarm on room sensor (Internal or external) Room2
RCPActual.RegioTimeGroupOccZone2
82
Time Group 'Occupied' (No. 1). Room2
RCPActual.RegioTimeGroupUnOccZone2
83
Time Group 'UnOccupied' (No. 2). Room2
RCPActual.RegioTimeGroupLightingZone2
84
Time Group 'Lighting' (No. 3). Room2
RCPActual.RegioExerciseOnHeat1
85
Valve Heat 1 in exercise
RCPActual.RegioExerciseOnHeat2
86
Valve Heat 2 in exercise
RCPActual.RegioExerciseOnCool1
87
Valve Cool 1 in exercise
RCPActual.RegioExerciseOnCool2
88
Not used
RCPActual.RegioExerciseOnHeatCool
89
Valve HeatCool in exercise
RCPActual.RegioExerciseOnHeat1Zone2
90
Valve Heat 1 in exercise
RCPActual.RegioExerciseOnHeat2Zone2
91
Valve Heat 2 in exercise
RCPActual.RegioExerciseOnCool1Zone2
92
Valve Cool 1 in exercise
RCPActual.RegioExerciseOnCool2Zone2
93
Not used
RCPActual.RegioExerciseOnHeatCoolZone2
94
Valve HeatCool in exercise
RCPActual.RegioDIOpenWindowCombined
95
Open window indication all Controllers
RCPActual.RegioDICondenseAlarmCombined
96
Alarm Condens indication all Controllers
RCPActual.RegioDIPresenceCombined
97
Pressens indication all Controllers (This is the combination of all pins
not actualy the presence state)
RCPActual.RegioDIChangeoverCombined
98
Change over indication all Controllers