Signal name
Modbus
address
Description
RCPActual.RegioHeat1DecOutput
19
Decrease heat 1 valve
RCPActual.RegioHeat1PulsPropOutput
20
Puls prop heat 1 valve
RCPActual.RegioHeat2IncOutput
21
Increase heat 2 valve
RCPActual.RegioHeat2DecOutput
22
Decrease heat 2 valve
RCPActual.RegioHeat2PulsPropOutput
23
Puls prop heat 2 valve
RCPActual.RegioCool1IncOutput
24
Increase cool 1 valve
RCPActual.RegioCool1DecOutput
25
Decrease cool 1 valve
RCPActual.RegioCool1PulsPropOutput
26
Puls prop cool 1 valve
RCPActual.RegioCool2IncOutput
27
Not used
RCPActual.RegioCool2DecOutput
28
Not used
RCPActual.RegioCool2PulsPropOutput
29
Not used
RCPActual.RegioHeatCoolIncOutput
30
Increase Heat cool valve
RCPActual.RegioHeatCoolDecOutput
31
Decrease Heat cool valve
RCPActual.RegioHeatCoolPulsPropOutput
32
Puls prop Heat cool valve
RCPActual.RegioSumAlarm
33
Sum alarm
RCPActual.RegioSumAlarmA
34
Sum alarm A
RCPActual.RegioSumAlarmB
35
Sum alarm B
RCPActual.RegioRoomTempControlState
36
Current controller state:
0=Heating
1=Cooling
RCPActual.RegioSunBlindsState
37
Blind Position:
0=In
1=Out
RCPActual.RegioPresence
38
Presence indication
RCPActual.RegioCO2Presence
39
Is set if presence if CO2 is high
RCPActual.RegioAIChangeOverState
40
Is set if change over from analog input
RCPActual.RegioChangeOverState
41
Is set if change over
RCPActual.RegioRoomTempSensorAlarm
42
Is set if sensor alarm on room sensor (Internal or external)
RCPActual.RegioTimeGroupOcc
43
Time Group 'Occupied' (No. 1).
RCPActual.RegioTimeGroupUnOcc
44
Time Group 'UnOccupied' (No. 2).
RCPActual.RegioTimeGroupLighting
45
Time Group 'Lighting' (No. 3).
RCPActual.RegioOpenWindowIndZone2
46
Open window indication Room2
RCPActual.RegioCondensationAlarmZone2
47
Alarm Condens indication Room2
RCPActual.RegioPresenceIndZone2
48
Pressens indication Room2
RCPActual.RegioFanSpeed1OutputZone2
49
Start Fan Speed 1 Room2
RCPActual.RegioFanSpeed2OutputZone2
50
Start Fan Speed 2 Room2
RCPActual.RegioFanSpeed3OutputZone2
51
Start Fan Speed 3 Room2
RCPActual.RegioLightingOutputZone2
52
Start signal Lighting Room2
RCPActual.RegioSunBlindsInOutputZone2
53
In signal Blind Room2
RCPActual.RegioSunBlindsOutOutputZone2
54
Out signal Blind Room2
RCPActual.RegioForcedVentOutputZone2
55
Start forced ventilation Room2
RCPActual.RegioHeat1IncOutputZone2
56
Increase heat 1 valve Room2
RCPActual.RegioHeat1DecOutputZone2
57
Decrease heat 1 valve Room2
RCPActual.RegioHeat1PulsPropOutputZone2
58
Puls prop heat 1 valve Room2
RCPActual.RegioHeat2IncOutputZone2
59
Increase heat 2 valve Room2
116
Regio
Ardo