Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioAlarmActive
381
3
1
Activate alarm and events function for EXOScada
0=Not active
1=Only alarm
2=Only events
3=Alarm and events is active
RCPSettings.RegioRemovableWallsCommPort
382
0
1
Port used for multiple controllers
RCPSettings.RegioRemovableWallsNSlaves
383
0
1
Number of slaves in the Network Max 4
RCPSettings.RegioRemovableWallsPLASlaves(0) 384
0
1
PLA Address Slaves
RCPSettings.RegioRemovableWallsPLASlave1
385
254
1
PLA Slave 1
RCPSettings.RegioRemovableWallsPLASlave2
386
254
1
PLA Slave 2
RCPSettings.RegioRemovableWallsPLASlave3
387
254
1
PLA Slave 3
RCPSettings.RegioRemovableWallsPLASlave4
388
254
1
PLA Slave 4
RCPSettings.RegioRemovableWallsELASlaves(0) 389
0
1
ELA Address Slaves
RCPSettings.RegioRemovableWallsELASlave1
390
31
1
ELA Slave 1
RCPSettings.RegioRemovableWallsELASlave2
391
32
1
ELA Slave 2
RCPSettings.RegioRemovableWallsELASlave3
392
33
1
ELA Slave 3
RCPSettings.RegioRemovableWallsELASlave4
393
34
1
ELA Slave 4
RCPSettings.RegioNRetries
394
3
1
Number of retries to read/write var from/to slaves
RCPSettings.RegioSlaveCommTimeOut
395
3
1
Minutes with missed comunication from master to a
slave consider that there is a comm failure and
revert back to control it's own outputs
RCPSettings.RegioRemoteRoomTemp
396
0
10
Communication Room Temperature Value
RCPSettings.RegioRemoteAIChangeOver
397
0
10
Communication Changeover Temperature Value
RCPSettings.RegioRemoteOutDoorTemp
398
0
10
Communication Outdoor Temperature Value
RCPSettings.RegioRemoteCondense
399
0
1
Communication Condensation Value
RCPSettings.RegioRemoteRoomCO2
400
0
1
Communication CO2 Value
RCPSettings.RegioRemoteRoomRH
401
0
1
Communication RH Value
RCPSettings.RegioRemoteSupplyAir
402
0
10
Communication Supply Air Temperature Value
RCPSettings.RegioRemoteRoomTempZone2
403
0
10
Communication Room Temperature Room2 Value
RCPSettings.RegioRemoteOutDoorTempZone2
404
0
10
Communication Outdoor Temperature Room2
Value
RCPSettings.RegioRemoteCondenseZone2
405
0
1
Communication Condensation Room2 Value
RCPSettings.RegioRemoteRoomCO2Zone2
406
0
1
Communication CO2 Room2 Value
RCPSettings.RegioRemoteRoomRHZone2
407
0
1
Communication RH Room2 Value
RCPSettings.RegioRemoteSupplyAirTempZone2
408
0
10
Communication Supply Air Temperature Room2
Value
Qsystem.Sec
409
-
1
System Time Seconds
Qsystem.Minute
410
-
1
System Time Minutes
Qsystem.Hour
411
-
1
System Time Hours
Qsystem.WDay
412
-
1
System WeekDay
Qsystem.Week
413
-
1
System Week
Qsystem.Date
414
-
1
System Date Day
Qsystem.Month
415
-
1
System Date Month
Qsystem.Year
416
-
1
System Date Year
Qsystem.PLA
417
254
1
Controller PLA Address
Qsystem.ELA
418
30
1
Controller ELA Adress
Regio
Ardo
manual, Rev. D
113