Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioRoomTempMaxDeviationLimit 352
20
1
Max allowed difference between setpoint and room
temp before alarm
RCPSettings.RegioAlarmHystZone2
353
0.2
10
Alarm hysteresis Room2
RCPSettings.RegioRoomTempHighLimitZone2
354
40
1
High room temp Room2
RCPSettings.RegioRoomTempLowLimitZone2
355
15
1
Low room temp Room2
RCPSettings.
RegioRoomTempMaxDeviationLimitZone2
356
20
1
Max allowed difference between setpoint and room
temp before alarm Room2
RCPSettings.RegioCondenseLimit
357
80
1
High limit for condense alarm
RCPSettings.RegioCondenseHyst
358
2
1
Condense alarm hysteresis
RCPSettings.RegioCondenseLimitZone2
359
80
1
High limit for condense alarm Room2
RCPSettings.RegioCondenseHystZone2
360
2
1
Condense alarm hysteresis Room2
RCPSettings.RegioCO2MaxLimit
361
1500
1
Max CO2 Level for Alarm
RCPSettings.RegioCO2MaxLimitZone2
362
1500
1
Max CO2 Level for Alarm Room2
RCPSettings.RegioPort1Func
363
2
1
Defines the function for Port1:
0=Not used
1=Exoline Master
2=Exoline Slave
3=ModBusMaster
4= ModBus Slave
5=Bacnet
6=Room Unit Display
RCPSettings.RegioBaud_Port_1
364
0
1
Bit rate Port 1
RCPSettings.RegioPort1Parity
365
1
1
Port 1 Parity
0=No Parity
1=Odd
2=Even
RCPSettings.RegioTimeOut_Port_1
366
0
1
Port 1 TimeOut
RCPSettings.RegioCharTimeOut_Port_1
367
0
1
Port 1 Char Time Out
RCPSettings.RegioPort2Func
368
1
1
Defines the function for Port2:
0=Not used
1=Exoline Master
2=Exoline Slave
3=ModBusMaster
4= ModBus Slave
5=Bacnet
6=Room Unit Display
RCPSettings.RegioBaud_Port_2
369
0
1
Bit rate Port 2
RCPSettings.RegioPort2Parity
370
1
1
Port 1 Parity
0=No Parity
1=Odd
2=Even
RCPSettings.RegioTimeOut_Port_2
371
0
1
Port 2 TimeOut
RCPSettings.RegioCharTimeOut_Port_2
372
0
1
Port 2 Char Time Out
RCPSettings.RegioMasterPort
373
0
1
-
RCPSettings.RegioRouterDefaultRoute
374
2
1
-
RCPSettings.RegioMin_PLA
375
0
1
-
RCPSettings.RegioMax_PLA
376
255
1
-
RCPSettings.RegioMin_ELA
377
0
1
-
RCPSettings.RegioMax_ELA
378
255
1
-
RCPSettings.RegioTCPIPMasterAnswerTimeout
379
25
1
-
RCPSettings.RegioModbusSlaveAddr
380
1
1
MODBUS slave address