Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioRUNoOfSelectMenus
324
8
1
Number of menus visible in the RU-DOS
RCPSettings.RegioRUNoOfDecimals
325
1
1
Number of decimal to be showed
RCPSettings.RegioRUDisplayBacklightTime
326
30
1
Time for backlight (sec)
RCPSettings.RegioRUButtonsUsed
327
7
1
Buttons that can be used in the RU
RCPSettings.RegioRUDisplayBacklightLow
328
20
1
Lightning Lo (0-255)
RCPSettings.RegioRUDisplayBacklightHigh
329
100
1
Lightning Hi (0-255)
RCPSettings.RegioRUDisplayContrast
330
15
1
Contrast (0-15)
RCPSettings.RegioRUTypeZone2
331
9
1
Room Unit attached to the controller Room2:
0=None
1=ED-RU
2=ED-RU-O
3=ED-RU-F
4=ED-RU-FO
5=ED-RU-DO
6=ED-RU-DFO
7=ED-RU-DOS
8=ED-RU-H
9=ED-RU-DOCS
10=ED-RUD
RCPSettings.RegioRUUserELASelectionZone2
332
0
1
User ELA Selection for Room Unit in Room2: 0=
Auto Detect
RCPSettings.RegioRUTempUnitZone2
335
1
1
Display Unit:
0=None
1=°C
2=°F
RCPSettings.RegioRUTemperatureCompZone2
336
0
1
Temperature Compensation for RU 2
RCPSettings.RegioRUDisplayViewTypeZone2
337
0
1
Select view mode for the display Room2:
0=Display value
1=Display Value with setpoint adjustment
2=Heat setpoint
3=Cool setpoint
4=Average cool/heat setpoint
5=Only setpoint offset
6=CO2 Level
RCPSettings.RegioRUDisplaySetPointTypeZone2 338
0
1
Select view mode for the display when pressing
increase decrease button Room2:
0=Setpoint offset
1=Controlling setpoint
2=Heat setpoint
3=Cool setpoint
RCPSettings.RegioRUSetPointAdjTimeOutZone2 339
5
1
Timeout for setpoint adjustment (sec)
RCPSettings.RegioRUMenuTimeOutZone2
340
10
1
Timeout for menu (sec)
RCPSettings.
RegioRUOnOffButtonLongPressTimeZone2
341
5
1
Time (sec) that On/Off button must be pushed
before Shutdown state
RCPSettings.RegioRUNoOfSelectMenusZone2
342
8
1
Number of menus visible in the RU-DOS
RCPSettings.RegioRUNoOfDecimalsZone2
343
1
1
Number of decimal to be showed
RCPSettings.
RegioRUDisplayBacklightTimeZone2
344
30
1
Time for backlight (sec)
RCPSettings.RegioRUButtonsUsedZone2
345
7
1
Buttons that can be used in the RU
RCPSettings.RegioRUDisplayBacklightLowZone2 346
20
1
Lightning Lo (0-255)
RCPSettings.RegioRUDisplayBacklightHighZone2 347
100
1
Lightning Hi (0-255)
RCPSettings.RegioRUDisplayContrastZone2
348
15
1
Contrast (0-15)
RCPSettings.RegioAlarmHyst
349
0.2
10
Alarm hysteresis
RCPSettings.RegioRoomTempHighLimit
350
40
1
High room temp
RCPSettings.RegioRoomTempLowLimit
351
15
1
Low room temp
Regio
Ardo
manual, Rev. D
111