Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioDigOutSelectSumAlarmA
304
2
1
Manual/Auto of SumAlarmA
RCPSettings.RegioDigOutSelectSumAlarmB
305
2
1
Manual/Auto of SumAlarmB
RCPSettings.RegioLightSelectZone2
306
2
1
Manual/Auto of Lighting Room2
RCPSettings.RegioSunBlindsInSelectZone2
307
2
1
Manual/Auto of BlindIn Room2
RCPSettings.RegioSunBlindsOutSelectZone2
308
2
1
Manual/Auto of BlindOut Room2
RCPSettings.RegioForcedVentSelectZone2
309
2
1
Manual/Auto of ForceVentilation Room2
RCPSettings.RegioDigOutSelectSumAlarmZone2 310
2
1
Manual/Auto of SumAlarm Room2
RCPSettings.
RegioDigOutSelectSumAlarmAZone2
311
2
1
Manual/Auto of SumAlarmA Room2
RCPSettings.
RegioDigOutSelectSumAlarmBZone2
312
2
1
Manual/Auto of SumAlarmB Room2
RCPSettings.RegioFanSelect
313
4
1
Fan speed Selected Remote/RegioTool:
0=Off
1=Speed1
2=Speed2
3=Speed3
4=Auto
RCPSettings.RegioFanSelectZone2
314
4
1
Fan speed Selected Remote/RegioTool
0=Off
1=Speed1
2=Speed2
3=Speed3
4=Auto
RCPSettings.RegioRUType
315
9
1
Room Unit attached to the controller:
0=None
1=ED-RU
2=ED-RU-O
3=ED-RU-F
4=ED-RU-FO
5=ED-RU-DO
6=ED-RU-DFO
7=ED-RU-DOS
8=ED-RU-H
9=ED-RU-DOCS
10=ED-RUD
RCPSettings.RegioRUUserELASelection
316
0
1
User ELA Selection for Room Unit: 0=Auto Detect
RCPSettings.RegioRUTempUnit
317
1
1
Display Unit:
0=None
1=°C
2=°F
RCPSettings.RegioRUTemperatureComp
318
0
1
Temperature Compensation for RU 1
RCPSettings.RegioRUDisplayViewType
319
0
1
Select view mode for the display:
0=Display value
1=Display Value with setpoint adjustment
2=Heat setpoint
3=Cool setpoint
4=Average cool/heat setpoint
5=Only setpoint offset
6=CO2 Level
RCPSettings.RegioRUDisplaySetPointType
320
0
1
Select view mode for the display when pressing
increase decrease button:
0=Setpoint offset
1=Controlling setpoint
2=Heat setpoint
3=Cool setpoint
RCPSettings.RegioRUSetPointAdjTimeOut
321
5
1
Timeout for setpoint adjustment (sec)
RCPSettings.RegioRUMenuTimeOut
322
10
1
Timeout for menu (sec)
RCPSettings.
RegioRUOnOffButtonLongPressTime
323
5
1
Time (sec) that On/Off button must be pushed
before Shutdown state