Signal name
Modbus
address
Default
value
Scale
Description
RCPSettings.RegioCVHeatExerciseHourZone2
237
15
1
Hour for exercise heating valve Room2
RCPSettings.RegioCVCoolExerciseHourZone2
238
15
1
Hour for exercise cooling valve Room2
RCPSettings.RegioCVHeatExerciseMinZone2
239
0
1
Minute for exercise heating valve Room2
RCPSettings.RegioCVCoolExerciseMinZone2
240
0
1
Minute for exercise cooling valve Room2
RCPSettings.RegioHeatExerciseTimeZone2
241
120
1
Time in seconds to Exercise the Heat Valves for
Room2
RCPSettings.RegioCoolExerciseTimeZone2
242
120
1
Time in seconds to Exercise the Cool Valves for
Room2
RCPSettings.
RegioSixWayValveFirstSeqFullyOpenZone2
243
0
10
6 Way valve tension (V) for fully open on 1st
sequence
RCPSettings.
RegioSixWayValveFirstSeqStartOpenZone2
244
3.3
10
6 Way valve tension (V) for start open on 1st
sequence
RCPSettings.
RegioSixWayValveSecondSeqStartOpenZone2
245
6.7
10
6 Way valve tension (V) for start open on 2nd
sequence
RCPSettings.
RegioSixWayValveSecondSeqFullyOpenZone2
246
10
10
6 Way valve tension (V) for fully open on 2nd
sequence
RCPSettings.
RegioSixWayValveCenterPointZone2
247
5
10
6 Way valve tension (V) for center point
RCPSettings.
RegioSixWayValveCenterPointHystZone2
248
2
1
6 Way valve centerpoint hysteresis (%)
RCPSettings.RegioAi1Comp
249
0
10
Analog input 1 compensation
RCPSettings.RegioAi2Comp
250
0
10
Analog input 2 compensation
RCPSettings.RegioAi3Comp
251
0
10
Analog input 3 compensation
RCPSettings.RegioAi4Comp
252
0
10
Analog input 4 compensation
RCPSettings.RegioCond_0V
253
0
1
Condense at 0 Volt input
RCPSettings.RegioCond_10V
254
100
1
Condense at 10 Volt input
RCPSettings.RegioCO2_0V
255
0
1
CO2 at 0 Volt input
RCPSettings.RegioCO2_10V
256
2000
1
CO2 at 10 Volt input
RCPSettings.RegioRH_0V
257
0
1
RH at 0 Volt input
RCPSettings.RegioRH_10V
258
100
1
RH at 10 Volt input
RCPSettings.RegioTempFilterFactor
259
0.2
100
Filter factor for temperature on analog input:
0=no filter
1=Max filter
RCPSettings.RegioCondFilterFactor
260
0.2
100
Filter factor for condense on analog input:
0=no filter
1=Max filter
RCPSettings.RegioCO2FilterFactor
261
0.2
100
Filter factor for CO2 on analog input:
0=no filter
1=Max filter
RCPSettings.RegioRHFilterFactor
262
0.2
100
Filter factor for RH on analog input:
0=no filter
1=Max filter
RCPSettings.RegioInternalTempComp
263
0
10
Internal temperature sensor compensation
RCPSettings.RegioCond_0VZone2
264
0
1
Condense at 0 Volt input for Room2
RCPSettings.RegioCond_10VZone2
265
100
1
Condense at 10 Volt input for Room2
RCPSettings.RegioCO2_0VZone2
266
0
1
CO2 at 0 Volt input for Room2
RCPSettings.RegioCO2_10VZone2
267
2000
1
CO2 at 10 Volt input for Room2
RCPSettings.RegioRH_0VZone2
268
0
1
RH at 0 Volt input for Room2
RCPSettings.RegioRH_10VZone2
269
100
1
RH at 10 Volt input for Room2