Regin RDAS-24C Series Скачать руководство пользователя страница 16

Variable list

Backup mode 513,

514,
515

In case the communication to the controller is lost, the device can be configured to go into a defined state.

Default setting mode is "keep last setpoint", i.e. in case of communication loss, the device controls to the
last received setpoint.

If the backup mode is enabled, it can be configured as follows:
- go to a predefined backup position
- keep current position

Restarting
the device

256

Restarting is possible by:

Power-reset (turning operating voltage off and on) or

by "ReInitDevice" command.
-> Device re-initializes and sets all process values to defaults.

Reset

The actuator supports the following re-initialization / reset behaviour:

Local reset by push-button

Remote reset: Using "RemoteFactoryReset" command

Effect of reset:
Process values: set to default values.

Parameters:
- Application and actuator parameters are set to factory defaults.
- Network parameters are reset only in case of local reset, not by remote reset (otherwise there will be
loss of communication).

Following parameters are not reset: Counters, status flags, device info, and factory data.

Self test

256

When triggered, the self test drives the actuator to the detected limits and sets the flags in register 769
according to the result (bit 09 = 1 -> "failed" or bit 10 = 1 -> "passed").
The self test is not passed when the limits were not reached from the lower end (results in jam). If the Min/
Max limits can be exceeded, the self test is not evaluated as failed.

16

RDAS…-24C variable list, Rev. A

Содержание RDAS-24C Series

Страница 1: ...en WE TAKE BUILDING AUTOMATION PERSONALLY VARIABLE LIST RDAS 24C...

Страница 2: ...rket as well as of how our products and systems function under the most variable conditions Every year Regin makes substantial investments in the development of our systems and HVAC products DISCLAIME...

Страница 3: ...Human machine interface RDAS5 24C and RDAS10 24C 8 3 1 1 Push button operation 8 3 1 2 LED colors and patters 8 3 1 3 Reset by push button 9 3 2 HMI Human machine interface RDAS7S 24C RDAS18S 24C RDA...

Страница 4: ......

Страница 5: ...tion Torque Max damper size Sound power level RDAS5 24C 24 V AC 20 28 V AC 50 60 Hz 3VA 2 5 W 150s 90 5 Nm 0 8 m2 28 dB RDAS10 24C 24 V AC 20 28 V AC 50 60 Hz 3VA 2 5 W 150s 90 10 Nm 1 6 m2 28 dB RDAS...

Страница 6: ...requirements Additionally ensure that the dampers are shut tight when in the fully closed position Fasten the actuator securely to avoid side load Check the rotary movement Manually set the damper by...

Страница 7: ...Comissioning notes Figure 2 1 Clockwise RDAS 24C variable list Rev A 7...

Страница 8: ...3 1 Display current address starting with lowest address digit Enter Modbus address with push button Press and hold button between 1 and 5 seconds See description in section 3 3 Push button addressing...

Страница 9: ...celled 4 After these 3 seconds LED shines red reset then green start up See section 3 3 Push button addressing for more information and examples 3 2 HMI Human machine interface RDAS7S 24C RDAS18S 24C...

Страница 10: ...life pulse without bus traffic flashing Normal operation life pulse with bus traffic Orange green 1 second orange 1 second green Device is in override control Orange 1 second on 1 second off Bus param...

Страница 11: ...D shines red confirmation release button An address can be stored at any time i e after setting the 1 digits or after setting the 1 and the 10 digits 5 Entered address is repeated one times for confir...

Страница 12: ...ED flashes red per button press 3 Store address skip 10 digit and 100 digit Press button until LED shines red address is stored and displayed 1 time for confirmation Figure 3 5 Example address 5 3 4 C...

Страница 13: ...s to 246 with push button press and hold between 5 and 10 seconds After addressing all devices the remaining configuration can be done over the bus using the default settings for bauderate auto baud a...

Страница 14: ...Timeout RW s 1 0 65535 516 Startup Setpoint RW 0 01 0 100 764 Modbus Address RW 1 247 255 unassigned 765 Baudrate RW 0 auto 1 9600 2 19200 3 38400 4 57600 5 76800 6 115200 766 Transmission Format RW 0...

Страница 15: ...er and function description Function Reg Description Override control 2 The actuator can be operated in override control for commissioning maintenance purposes or system wide functions e g night cooli...

Страница 16: ...initialization reset behaviour Local reset by push button Remote reset Using RemoteFactoryReset command Effect of reset Process values set to default values Parameters Application and actuator paramet...

Страница 17: ...RDAS 24C variable list Rev A 17...

Страница 18: ...Regin All rights reserved HEAD OFFICE AB Regin Box 116 SE 428 22 K llered Visiting address Bang rdsv gen 35 SE 428 36 K llered Phone 46 0 31 720 02 00 Fax 46 0 31 720 02 50 info regincontrols com www...

Отзывы: