1409
ASN [Char_16…15]
R
Each register: Two
bytes, each coding
an ASCII char.
ASN is coded
beginning with reg.
1409
Example:
0x47 44 = GD
0x42 31 = B1
0x38 31 = 81
0x2E 31 = .1
0x45 2F = E/
0x4D 4F = MO
-> ASN is GDB181.1E/MO
1410
ASN [Char_14…13]
R
1411
ASN [Char_12…11]
R
1412
ASN [Char_10…9]
R
1413
ASN [Char_8…7]
R
1414
ASN [Char_6…5]
R
1415
ASN [Char_4…3]
R
1416
ASN [Char_2…1]
R
Reserve
4.1.1
Register 769 "Status"
Status
Bit 00
1 = reserved
Bit 06
1 = Adaption done
Bit 01
1 = Backup mode active
Bit 07
1 = Adaption in progress
Bit 02
1 = reserved
Bit 08
1 = Adaption error
Bit 03
1 = reserved
Bit 09
1 = Selftest failed
Bit 04
1 = Mechanical fault, device jammed or
manual override
Bit 10
1 = Selftest passed
Bit 05
1 = Nom. lifetime exceeded
Bit 11
1 = Invalid configuration
4.1.2
Supported function codes
Function codes
03 (0x03)
Read Holding Registers
04 (0x04)
Read Input Register
06 (0x06)
Write Single Register
16 (0x16)
Write Multiple Registers (Limitation: Max. 120 registers within one message
4.2 Parameter and function description
Function
Reg.
Description
Override
control
2
The actuator can be operated in override control for commissioning / maintenance purposes or system-wide
functions (e.g. night-cooling).
✓
Manual override: When the gear disengagement is used to freely adjust the damper position, a mechan-
ical jam will be detected if a mismatch between setpoint and actual position persists for more than 10
seconds.
✓
Remote override: The actuator enters this state when an override command is sent over the bus
✓
Available commands:
- Open /Close (depends on opening direction)
- Min / Max (depends on Min/Max settings)
- Stop
Adaptive
positioning
258
✓
For air dampers where the opening range is smaller than the nominal opening range 0…90°, the feedback
signal can be adapted to have the actual opening range represented as 0…100%.
✓
Using adaptive positioning makes the actuator driving to its end positions at the first startup after acti-
vating the adaptive positioning.
✓
To trigger the adaptation again after the first startup, either the command "CalibrateAdaption" (Write "1"
into register no. 256), or the adaptive positioning can be turned off and on again.