INSTRUCTION
RCW-M32
IN20015 REV. C, 2019-05-28
C
Caauuttiioonn!! Read and understand the instruction before using the product.
C
Caauuttiioonn!! Ensure that the installation complies with local safety
regulations.
C
Caauuttiioonn!! Before installation or maintenance, the power supply should first
be disconnected. Installation or maintenance of this unit should only be
carried out by qualified personnel. The manufacturer is not responsible
for any eventual damage or injury caused by inadequate skills during instal-
lation, or through removal of or deactivation of any security devices.
Technical Data
Supply voltage
24 V AC/DC (21…27 V AC/DC)
Frequency
868 MHz
Protection class
IP54
Ambient temperature
-10…+50 °C
Ambient humidity
Max. 85 % RH, non-condensing
Dimensions, external (WxHxD)
120 x 112 x 40 mm
Internal serial port, type
RS485, isolated
Internal serial port, built-in protocol
Modbus
Internal serial port, communication
speed
1200 / 2400 / 9600 (default) / 19200 /
38400 /57600 bps
Internal serial port, parity
None (default) / even / odd
Internal serial port, stop bit
1 stop bit (default) / 2 stop bit
Installation
1. Lift the lid to access the terminals.
2. Connect the receiver to the master controller via the RS485
terminal.
3. Connect the receiver to the supply voltage. The display will beep
once and two small LED lights will start blinking on the display.
4. Mount the receiver on any flat surface. If it is installed in a humid
environment, vertical mounting is recommended.
When the receiver is powered on it will automatically forward signals
received from the paired sensors and detectors to the controller.
Wiring
Number
Description
1
Display
2
Joystick with
Menu button
3
Supply voltage terminal
4
RS485 terminal
Settings
The joystick is used to manoeuvre through the channels (see
).
For each selected channel four different values are shown subsequently
in the display:
1. Current channel, e.g. 01
2. Received signal strength indicator (RSSI),
S.1…9
S.
= signal strength,
1
= weak signal,
9
= strong signal
S.-
= no sensor is paired on the selected channel
Note that the signal strength abbreviation
S.
should not be mistaken
for number
5
.
3. Value 1 for the sensor or detector (if available),
0
…
99
. If both value
1 and 2 are available, value 1 always shows the temperature.
4. Value 2 for the sensor or detector (if available),
0
…
99
. Value 2 can
for example show the humidity.
Table 1 Navigate the channels
Description
Manoeuvre
Time
Activate the display
Press the
Menu
button
1 s
Move to the subsequent channel.
Push UP
1 s
Move to the preceding channel.
Push DOWN
1 s
Jump 8 channels forward.
Push RIGHT
1 s
Leave the menu and inactivate the display.
Push LEFT
3 s
Many default settings can be changed via the display. The joystick is used
to navigate within the menu as shown in
. To enter the menu,
press the
Menu button
4 s when the display is inactive. Six levels are
available:
1. A: Pair and unpair sensors
2. B: Modbus addresses, as hexadecimal numbers
3. C: Communication speed (baud rate)
4. D: Parity and stop bit
5. E: Selected frequency
6. F: Current software version
Table 2 Navigating the menu
Description
Manoeuvre
Time
Enter into the menu
Press the
Menu button
when
the display is inactive
4 s
Move between the different levels in
the menu (A-F)
Push UP or DOWN
1 s
Enter into one level
Press the
Menu button
1 s
Move between different values within
one level
Push UP or DOWN
1 s
Leave the menu and inactivate the
display.
Push LEFT
3 s
A complete description on how to read and modify the settings, both via
the display and via Modbus, can be found in the Modbus variable list.
4
3
GND A- B+
G
G0
1
2
RCW-M32
1