RCF-230AD

2

Setpoint limitation

In parameters 34 and 35, it is possible to set the maximum allowed 
setpoint increase and decrease respectively. 
Example: If P35=5 and P34=3, the setpoint can be changed between 
17°C and 25°C (see the picture below).

Example of setpoint limitation

Fan control

The fan can be controlled via RCF-230AD with the following modes: 
Low speed, Medium speed, High speed, Auto. The current fan speed 
in the Auto mode depends on the heating or cooling demand and the 
settings for each speed. 
When using automatic control, ”AUTO” is shown in the display.
The number of fan speed steps can be selected via parameter 30. If 

the parameter is set to 1, the first fan speed step will be used for fan 

control. 
Via parameter 31, it is possible to set the fan to the lowest speed level 
when Auto mode is selected. If this parameter is set to 1, the fan will 
run in all operating modes except Off (unless mould protection is ac-
tive, in which case the fan will run in Off mode as well).

Manual control of the fan speed

By pressing the fan button, you change the fan speed according to 
the sequence I

à

II

à

III

à

AUTO. When using manual control, ”MAN” is 

shown in the display.

Indications

The display has the following indications:
HEAT   Heating control
COOL   Cooling control

       The open window symbol is shown if this function has  

 

been configured and a window is open. 

OFF   The controller does not heat or cool

On/Off button

By pressing the On/Off button, RCF-230AD will switch between Off 
mode and Comfort/Economy mode.

Parameter list

It is possible to set different parameter values in a parameter list. The 
parameter list is accessed by simultaneously holding the INCREASE and 
DECREASE buttons depressed for about 5 seconds until the Service 
symbol is displayed and then pressing the INCREASE button twice. 
First the display will show parameter 1. Use the INCREASE and DE-
CREASE buttons to scroll between the parameters and press the On/Off 
button to select the desired parameter. The parameter number will then 
be replaced by the parameter value. The value can be changed using the 
INCREASE and DECREASE buttons. If a button is held depressed the 

value will start scrolling, first slowly and then with increasing speed.

To exit the parameter list and go back to the basic display, press the IN-
CREASE button until “EXIT” is shown (one step before parameter 1) and 
press the On/Off button. You can also exit the parameter list by pressing 
down the INCREASE and DECREASE buttons simultaneously.

Parameters

The following parameters can be changed in the parameter list:

Para-

meter 

number

Description

FS 

(factory 

setting)

1

Control mode:
2=2-pipe system 
3=4-pipe system 

 

4=Electric heater 

(not valid for this model)

3

2

Change-over mode: 
0=Heating control, 1=Cooling control, 2=Au-
tomatic change-over depending on ana-
logue temperature sensor or digital input

2

3

Operating mode when activating digital 
input 1:
0=Economy mode (occupancy)
1=Off mode (window)

0

4

Mould protection:
0=Not active
1=Active (fan never stops)

0

5

Neutral zone at Comfort mode (NZC). If the 
neutral zone is 2 K, the heating setpoint is 
equal to the setpoint minus 1 and the cool-
ing setpoint is equal to the setpoint plus 1.

2 K

6

Heating setpoint when unoccupied.

15°C

7

Cooling setpoint when unoccupied.

30°C

8

P-band for the room controller.

10 K

9

I-time for the room controller.

300 s

10

Not valid for this model

11

Switch off timer for Comfort mode.

0 min

12

Switch on delay for Comfort mode.

0 min

13

Sensor connected to AI1:
0=Internal sensor, 1=External room sensor

0

14

Sensor connected to UI1:
0=None, 1=Change-over digital, 2=Change-
over analogue

0

15

Not valid for this model

16

Output signal for actuator connected to 
AO1: 
0=0...10V, 1=2...10V, 2=10...2V, 3=10...0V

0

17

Output signal for actuator connected to 
AO2: 
0=0...10V, 1=2...10V, 2=10...2V, 3=10...0V

0

18

Not valid for this model

19

Not valid for this model

20

Not valid for this model

21

Not valid for this model

22

Time in hours between exercise of heating 
actuator.

23

23

Time in hours between exercise of cooling 
actuator.

23

24

Setpoint or actual value shown in the 
display: 
0=Actual, setpoint when changing the set-
point, 1=Actual, setpoint adjustment when 
changing the setpoint, 2=Setpoint, 3=Only 
the setpoint adjustment

2

25

Configuration of fan control:

0=No control, 1=The fan is controlled by the 
heating requirement, 2=The fan is control-
led by the cooling requirement, 3=The fan 
is controlled by the heating and cooling 
requirement
When using an electric heater, this param-
eter should only be set to 1 or 3, or the 
heater may be overheated.

3

26

Start signal in % of the controller output, 
heating or cooling, for fan speed 1.

20 (5 
when 
using an 
electric 
heater)

27

Start signal in % of the controller output, 
heating or cooling, for fan speed 2.

60

Содержание RCF-230AD

Страница 1: ...oximity to the con troller and within easy reach of the operator and should be marked as the disconnecting device for the equipment Always use the circuit breaker to disconnect the controller from the mains supply during maintenance of the fan coil and actuators Settings Control modes RCF 230AD has control modes Heating and Cooling in sequence or seasonal switching between heating and cooling chan...

Страница 2: ... press the IN CREASE button until EXIT is shown one step before parameter 1 and press the On Off button You can also exit the parameter list by pressing down the INCREASE and DECREASE buttons simultaneously Parameters The following parameters can be changed in the parameter list Para meter number Description FS factory setting 1 Control mode 2 2 pipe system 3 4 pipe system 4 Electric heater not va...

Страница 3: ...lly open NC normally closed Wiring 10 20 30 LOGIC 40 50 POWER Bottom plate connections Connection diagrams for RCF 230AD 10 L 230 V AC Line Power supply 11 NC Not connected 12 N 230 V AC Neutral Power supply internally con nected to terminal 13 13 N Fan coil common 230 V AC Neutral Common fan coil connec tor internally connected to terminal 12 20 DO1 Fan coil output 1 for fan control Relay 230 V A...

Страница 4: ... och SÄNKA knapparna Parameter 24 bestämmer vad som visas i displayen Se parameterlistan för detaljer Då man väljer att börvärdesförskjutningen ska visas är grundbörvär det 22 C Börvärdesbegränsning I parameter 34 och 35 går det att ställa in den maximalt tillåtna höjnin gen respektive minskningen av börvärdet Exempel Om P35 5 och P34 3 kan börvärdet ändras mellan 17 C och 25 C se nedanstående bil...

Страница 5: ...är värmebörvärdet lika med börvärdet minus 1 och kylbörvärdet lika med börvärdet plus 1 2 K 6 Värmebörvärde vid frånvaro 15 C 7 Kylbörvärde vid frånvaro 30 C 8 P band för rumsregulatorn 10 K 9 I tid för rumsregulatorn 300 s 10 Gäller ej denna modell 11 Frånslagstimer för Komfortläge 0 min 12 Tillslagsfördröjning för Komfortläge 0 min 13 Givare ansluten till AI1 0 Intern givare 1 Extern rumsgivare ...

Страница 6: ...Relä 230 V AC 3 A 21 DO2 Fan coil utgång 2 för fläktstyrning Relä 230 V AC 3 A 22 DO3 Fan coil utgång 3 för fläktstyrning Relä 230 V AC 3 A 30 33 NC Ej ansluten 40 DI Digital ingång Potentialfri fönsterkontakt el ler närvarokontakt Konfigur erbar för NO NC 41 0 V Analog jord 42 AI Analog ingång Extern PT1000 istället för intern NTC 43 UI Universell ingång Change over ingång Poten tialfri omkopplar...

Страница 7: ...RCF 230AD verfügt über die Regelmodi Heizen und Kühlen in Sequenz oder jahreszeitliches Umschalten zwischen Heizen und Kühlen Change Over siehe unten Change Over Funktion RCF 230AD hat einen Change Over Eingang der den Ausgang AO1 je nach Bedarf automatisch auf Heizen oder Kühlen umstellt An den Eingang kann ein Pt1000 Fühler angeschlossen werden der so montiert werden muss dass die Vorlauftempera...

Страница 8: ...iste geändert werden Para meter nummer Beschreibung Werks einstellung WE 1 Regelmodus 2 2 Rohr System 3 4 Rohr System 4 Elektr Erhitzer nicht gültig für dieses Modell 3 2 Change Over 0 Regelung Heizen 1 Regelung Kühlen 2 Automatischer Change Over über analo gen Temperaturfühler oder Digitaleingang 2 3 Betriebsmodus bei aktiviertem DI 1 0 Eco Präsenz 1 Abschaltbetrieb Fenster 0 4 Schimmelschutzfunk...

Страница 9: ...ter Fan Coil 230 V AC Gemeinsamer Fan Coil Anschluss intern mit Klemme 12 verbunden 20 DO1 Fan Coil Ausgang 1 für Ventilator ansteuerung Relais 230 V AC 3 A 21 DO2 Fan Coil Ausgang 2 für Ventilator ansteuerung Relais 230 V AC 3 A 22 DO3 Fan Coil Ausgang 3 für Ventilator ansteuerung Relais 230 V AC 3 A 30 33 Nicht verbunden 40 DI Digitaleingang Potenzialfreier Fenster oder Präsenzkontakt Einstellba...

Страница 10: ...pose d un mode Chauffage et d un mode Refroidisse ment qui fonctionnent soit en séquence soit en fonction d un changement saisonnier fonction change over Fonction change over RCF 230AD est doté d une entrée pour la fonction change over Cette dernière permet d utiliser la sortie AO1 pour commander soit le chauffage soit le refroidissement en fonction du besoin Cette entrée peut aussi être raccordée...

Страница 11: ...nez le bouton appuyé les chiffres se mettent à défi ler d abord lentement puis plus vite Pour quitter la liste des paramètres et revenir l écran d accueil appuyez sur la touche AUGMENTER jusqu à ce que EXIT s affiche à l écran juste avant le paramètre 1 puis appuyez sur le bouton de marche arrêt Vous pouvez aussi appuyer simultanément sur les touches AUGMEN TER DIMINUER Paramètres Les paramètres s...

Страница 12: ...ante interne 0 K 34 Ajustement maximum autorisé de la valeur de consigne vers le haut augmenter Réglable 0 13 K Valeur de la consigne par défaut 22 C 13 K 35 Ajustement maximum autorisé de la valeur de consigne vers le bas diminuer Réglable 0 17 K Valeur de la consigne par défaut 22 C 17 K 36 État de l entrée digitale 1 DI1 NO NF 0 NO 1 NC 0 37 État de l entrée universelle 1 UI1 NO NF 0 NO 1 NC 0 ...

Страница 13: ... tiel configurable NO NF ou PT1000 44 0 V Terre analogique 50 0 V Terre analogique 51 AO1 Sortie analogique 1 52 AO2 Sortie analogique 2 53 NC Réservé pour une utilisation future 54 NC Réservé pour une utilisation future Protection par fusible équivalent à la somme des courants entre DO1 DO3 Sécurité électrique et EMC Ce produit est conforme aux exigences du standard européen EN60730 1 2 9 et port...

Отзывы: