Consult documentation in all cases where this symbol is used, in order to fi nd 

out the nature of the potentional hazards and any actions to be taken. Installa-

tion and maintenance of this unit should only be carried out by skilled workers. 

The manufacturer is not responsible for any damages caused by inadequate 

skills during installation and/or by any safety devices having been removed or 

tampered with.

Always protect the pressure regulator by using strainers upstream of the valve. Make sure 

that the water quality complies with UNI 8065 standards (Fe < 0.5 mg/kg and 

Cu < 0.1 mg/kg). Furthermore, the maximum iron oxide in the water passing through the 

control valve (PICV) should not exceed 25 mg/kg (25 ppm). To ensure the main pipework is 

cleaned appropriately, fl ushing by-passes should be used without fl ushing through the pres-

sure regulator of the PICV thereby preventing debris that might clog the valve.

During cleaning operation of the valve use a damp cloth, 

do not 

use any detergent or che-

mical solvent that could seriously damage the parts.

For some valve models, depending on the max. set fl ow rate, noise above 50 dB may be 

generated at high differential pressure values.

PCMTV50-150

1

2

2

3

4

B

N

O

1

6

Box 116, SE-428 22 Kållered, Sweden

Tel: +46 31 720 02 00, Fax: +46 31 720 02 50

www.regincontrols.com, [email protected]

Technical data

PCMTV50-F20

PCMTV65-F30

PCMTV80-F30

PCMTV100-F55

PCMTV125-F90

PCMTV150-F90

PCMTV150-F150

Max. fl ow rate

20000 l/h /

5.55 l/s

30000 l/h /

8.33 l/s

30000 l/h /

8.33 l/s

55000 l/h /

15.2 l/s

90000 l/h /

25 l/s

90000 l/h /

25 l/s

150000 l/h /

41.6 l/s

Flow accuracy 

[∆p 0.3 ÷ 1 bar]

±5 %

±5 %

±5 %

±5 %

±5 %

±5 %

±5 %

Start-up 

∆p →Q=const.

30 kPa /

0.30 bar

30 kPa / 

0.30 bar

30 kPa / 

0.30 bar

30 kPa / 

0.30 bar

35 kPa  / 

0.35 bar

50 kPa / 

0.50 bar

50 kPa / 

0.50 bar

Max. ∆p

400 kPa / 4 bar

400 kPa / 4 bar

400 kPa / 4 bar

400 kPa / 4 bar

400 kPa / 4 bar

400 kPa / 4 bar

400 kPa / 4 bar

Temperature

-10...+120°C

-10...+120°C

-10...+120°C

-10...+120°C

-10...+120°C

-10...+120°C

-10...+120°C

Max. working 

pressure

1600 kPa /

16 bar

1600 kPa /

16 bar

1600 kPa /

16 bar

1600 kPa /

16 bar

1600 kPa /

16 bar

1600 kPa /

16 bar

1600 kPa /

16 bar

Connections

EN1092-2

EN1092-2

EN1092-2

EN1092-2

EN1092-2

EN1092-2

EN1092-2

i

Flow

Read this instruction before installation of the product. 

Subject to change without notice.

Valve installation direction and actuator mounting/disassembly

Mounting nut

Mounting instructions

1. 

Check the wiring and ensure the actuator supply voltage is disconnected.

2. 

Place the mounting assembly over the stem and then slot the actuator onto it. 

Ensure the mounting nut is level, as screws can otherwise break or come loose.

3. 

Raise the mounting installation all the way to the top of the stem and secure the 

actuator fi rmly by turning the mounting nut. 

Do not tighten the nut too hard!

4. 

Secure the screws to mount the entire installation and actuator into place.

Disassembly takes place in reverse order.

NOTE: 

The valve has to be mounted with the arrow in the direction of the fl ow.

Mounting it in the wrong direction may damage the system and the valve itself.

If fl ow reversal is possible, a non-return valve should be mounted.

1

Содержание PCMTV50-F20

Страница 1: ...e 20000 l h 5 55 l s 30000 l h 8 33 l s 30000 l h 8 33 l s 55000 l h 15 2 l s 90000 l h 25 l s 90000 l h 25 l s 150000 l h 41 6 l s Flow accuracy p 0 3 1 bar 5 5 5 5 5 5 5 Start up p Q const 30 kPa 0...

Страница 2: ...Setting Indication De nition Operation Explanation Select input indication type Flow input Finish by pressing MODE button after selection Control by INT mode volume input Control by INT mode Input to...

Страница 3: ...inear curve ow value conversion according to rst graph Equal percentage curve ow value conversion according to second graph Control according to curve Min contol voltage calibration Min voltage analog...

Страница 4: ...emove the actuator and actuator assembly and then loosen the stem completely by turning it anti clockwise 4 Apply lubricant to the thread of the valve stem recommended lubricant is TAS 100EP solid lm...

Страница 5: ...urch uss 20000 l h 5 55 l s 30000 l h 8 33 l s 30000 l h 8 33 l s 55000 l h 15 2 l s 90000 l h 25 l s 90000 l h 25 l s 150000 l h 41 6 l s Durch ussgenau igkeit p 0 3 1 bar 5 5 5 5 5 5 5 Inbetriebnahm...

Страница 6: ...ng Anzeige Typ Volumenstromeingang Nach der Auswahl beenden durch Dr cken der MODE Taste Steuerung durch INT Mode Volumen Eingang Steuerung durch INT Mode Auswahl Eingabewerk zeug Spannungseingang Fes...

Страница 7: ...den durch Dr cken der MODE Taste Lineare Kurve Konvertierung des Durch usswertes gem des ersten Graphen Gleichprozentige Kurve Konvertie rung des Durch usswertes gem des zweiten Graphen Regelung gem d...

Страница 8: ...g zur Spin del indem Sie sie gegen den Uhrzeigersinn drehen 4 Tragen Sie Schmiermittel auf die Spindel auf empfohlenes Schmiermittel w re TAS 100EP solid lm lubrication grease 5 Nachdem Sie das Schmie...

Отзывы: